    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #1

    Oct 20, 2008, 10:01 AM
    Goodman gmp board blinks three times
    Blinks three times

    My goodman furnace does not ignite the HSI, and the board blinks three times. Is this the pressure switch or rollover, or perhaps something else
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #2

    Oct 20, 2008, 10:06 AM

    My furnace is a Goodman GMP 100-3
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #3

    Oct 20, 2008, 10:51 AM
    3 blinks is end switch closed without inducer on.

    Check venter end switch.

    Also see the back of the blower for a wiring diagram with the blink codes listed.
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #4

    Oct 20, 2008, 11:11 AM

    I changed the pressure switch, and still got the three blinks. So I disconnected the tube and sucked on it to close the pressure switch, causing it to ignite the HSI. The inducer is running but apparently not creating a vacuum to the pressure switch. Could this be clogged? Do I need to take off the inducer and clean that port?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Oct 20, 2008, 11:36 AM
    Could this be clogged? Yes but you might check the connecting tube for cracks first.
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #6

    Oct 20, 2008, 02:43 PM
    As it turns out, the inducer on the unit itself was not working. There was a secondary inducer that was causing it primary inducer to spin, but it was not coming on. I have changed the primary inducer, and now cannot get the primary inducer to work. What is the line voltage on the primary inducer. I am reading around 5vac between the white and black lines. What should it be.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #7

    Oct 20, 2008, 03:12 PM
    If I am not mistaken the inducer runs on 120 volts. How about posting a correct model number so we can check.
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #8

    Oct 20, 2008, 03:18 PM
    The model number is GMP 100-3, and it is about 10 years old
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #9

    Oct 20, 2008, 04:46 PM
    120 volts is the answer I found
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #10

    Oct 20, 2008, 04:57 PM
    When I pull the wires off the vent motor mounted on the furnace, I measure about 5vac between the black and white wires. So would the problem be in the circuit board? According to the schematic, I should read 120vac. In the schematic, there is also a power vent relay. Is that on the board?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #11

    Oct 20, 2008, 07:11 PM
    In the schematic, there is also a power vent relay. Is that on the board?

    Yes and it is possible it is defective.
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #12

    Oct 21, 2008, 06:34 AM
    If that is on the board, and defective, does that mean I have to replace the whole board?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #13

    Oct 21, 2008, 09:38 AM
    If that is on the board, and defective, does that mean I have to replace the whole board?

    Usually that is the solution since the relay is usually soldered to the board and not easily found at radio shack.
    zenbones's Avatar
    zenbones Posts: 8, Reputation: 1
    New Member
     
    #14

    Oct 22, 2008, 02:51 PM
    Usually that is the solution since the relay is usually soldered to the board and not easily found at radio shack.[/QUOTE]

    Replaced the whole board, and now enjoying heat once again. Thanks for all your help, you have been great.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

New Furnace Circuit Board Flash Solid 5 Sec. Then blinks [ 8 Answers ]

I just installed a new Circuit board in my Carrier Furnace. When I tested having only the White wire to CON and the Red wire to Y. The RED light Flashes Sold RED for 5 sec. and then flashes. The Component Test does run successfully. I'm not clear why the LED light first flashes sold for 5 sec....

Goodman Furnace Three times to start? [ 1 Answers ]

I installed a Goodman Gas furnace last year, and also installed the factory LP Gas conversion kit (gas valve regulator spring, and orifices). This furnace is installed on the second floor of my house, and the house has three other devices that are also fed from the same LP Gas tank. The tank is...

Furnace do not truns on LED blinks three times [ 1 Answers ]

I have Goodman Furnace model GMT 090- 3B installed 3 years ago and it gives me constant problem I just changed Hot surface ignitor last week and it was working good and it again stop working and when I open the cover of furnace I can see there is a red LED light that blinks three times and stops...

Two blinks on Goodman PGB030075-1, what's wrong? [ 3 Answers ]

Any ideas?? It's cold outside (42 degrees), the wife and three kids are home for the day/night and I have to go to work at 1630. The last time I had someone come to look at this unit, they said I needed a new unit, then got a second opinion and an eight dollar part fixed it. Leary of having a...

Why does the furnace not work and LED blinks three times [ 2 Answers ]

Why does the furnace not work suddenly after one year and the LED blinks three times


View more questions Search