    Goodman Furnace -takes 2 Or 3 Ignition Cycles B4 Stays Running
    Hi,hope you can help me out.i have a goodman manufacturing forced air furnace that i believe is giving me a warning sign of a future failure.what has happened is in this order,1st one morning the thermostat showed that the furnace was on and it was'nt.turned it off and then back on at the thermostat and the furnace turned on like nothing was wrong.2nd another morning found the furnace on but this time all it was doing was blowing cold air(went to look at furnace and found blowers on but not the burner).once again turned it off at the thermostat and back on again and it worked again.3rd and most important i feel is that while taking a good look at how the furnace was operating at start up i noticed this-exhaust blower turns on,ignitor activates,burners lite,3-5 seconds later the burner shuts off(like the gas is shut off suddenly),wait 20-30 seconds and the ignitor re-activates and the burner lites.once again 3-5 seconds later the burner shuts off,waited and watched 20-30 seconds and once again the ignitor re-activated and lit the burner and finally on the third time the burner stayed lit.now ,the thermostat was replaced before the heating season(nothing wrong with old one just wanted one more up to date)and i recently exchanged it for a new one thinking that might be the problem.well the problem still exists,vacuumed out furnace and replaced filter,checked the light for any flashing codes and all that it was doing is a steady pulse that indicates normal operation.this problem is not very consistent though,sometimes it operates just fine.hoping not to be in the cold in the future,thanks chris...
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Jan 7, 2007, 08:09 AM
    Dirty flame sensor probably
    matheny76's Avatar
    matheny76 Posts: 1, Reputation: 1
    New Member
     
    #3

    Dec 11, 2010, 08:15 AM
    I have been having the same problem with my Goodman. Sometimes (at night usually when we are sleeping ) the burner fails to stay running at all , just goes through the short cycles then stops. I have a steady red light though not a pulse. Also , I noticed that when I have the top access panel open to view the operation of the burners and when the weather is a bit warmer than our current outside temp of 20's it works fine. Last year I had to replace the igniter and also replaced the thermostat with a newer model. I change my filters about every 2 weeks and do a good vacuuming each season before I fire it up. I will pick up a flame sensor today and try it out. Does anyone know if this corrected the issue for junior fan?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace stays on for 2 minutes [ 2 Answers ]

I have a digital thermostat and my furnace seems to stay on for only 2 minutes at a time. It does this approximately every 10 min. The programmed cycle rate is 5/hr, so starting up every 10 min makes sense. If the programmed temp is 72 F and the room temp is around 72 F, it will start up as...

Buzzing sound stays on for a few minutes when Furnace starts! [ 2 Answers ]

Hi, My gaz furnace is 2 years old and it was running smoothly last year. This year however, it started making a buzzing sound when it starts up. The sound stays for a few minutes and then stops when the heat as been blowing a few seconds. Could anyone give me advice on what this noise...

Whirlpool dryer takes several cycles to dry [ 1 Answers ]

Here are the specs on my dryer, which is about 6 months past warranty: Type: DWSR-ELE-2406028-CV54 Serial: MR3413983 Model: LEQ9508PWO I verified that its exhaust duct and lint filter are clear of debris. Cleaning out the exhaust duct, I did notice that the lint in there was damp, but...

Furnace Pilot stays lit continuously [ 1 Answers ]

My furnace pilot stays lit continuously Even though it states inside of the furnace and I quote "Pilot will light automatically when there is a call for heat. NOTE during thermostat off cycle main burners and PILOT flame are both extinguisehd. I have gotten many rude response that say that's...

Furnace blower cycles with Thermostat off [ 2 Answers ]

Have Goodman Furnace built 1994. Worked fine until about 3 weeks ago. It starts cycling, and the heat icon does not show on the thermostat. I turn the thermostat off, the furnace continues to blow. Last night to verify, took the thermostat off the wall (but still had the furnace plugged in and...


View more questions Search