    Goodman furnace gmp
    Ok. I can turn the thermostat to 72 and it will stay on 64 with the fan blowing constant. Burners aren't firing. On the control board for the furnace, there is a trouble shooting light that blinks to tell you what is wrong. It blinks four times which indicates an "Open Limit Switch", and it tells to check the "main limit open", or the aux limit open". Well, where are those and is this going to b tough and expensive?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Jan 30, 2006, 11:00 AM
    Maybe an easy one I can solve. The limit switches will be in the heat exchanger. They let the control board know something is wrong because it is too cold or too hot. Maybe an oval thing with 2-3 wires going back to the control board. Pull them out and take to an electrical or heating supply and they should have new ones.
    czombos47's Avatar
    czombos47 Posts: 2, Reputation: 0
    New Member
     
    #3

    Jan 30, 2006, 11:12 AM
    Is there any site I can go to that would have the discription or loctation of the heat exchanger, or the oval part with the limit switc:confused: :confused: he's located?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Jan 30, 2006, 11:24 AM
    You might find a diagram on the Goodman site. Usually you can see the blower and control board when you open the panel to change air filters. The blower pulls air in the center and out the side away from the filters into the heat exchanger.
    wheatnbarley24's Avatar
    wheatnbarley24 Posts: 63, Reputation: 3
    Junior Member
     
    #5

    Jan 30, 2006, 05:46 PM
    You might want to make sure your filter and cooling coils are clean also your exchangers and flu pipe. Lack of air flow is the main cause of a limit tripping
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #6

    Jan 30, 2006, 07:22 PM
    If you furnace is an upflow model the main limit should be on the furnace just about the bburners. It si a flat sheet of micarda like material about one inch by one and a half inch with two wires attached. You can short across the to contacts where the wires are connected and if the blower stops running then the limit is bad. If it continues to run there is another check point in the same location. On one of the wires there is a little firecraker type fuse that is to protect if the flame rolls out the front of the furnaces burners. If you will short out the wire on either side of the fuse and the blower stops then this is the problem. This is the way Carrier furnaces are wired and I am sure that Goodman have something similar.
    RIBBS4's Avatar
    RIBBS4 Posts: 6, Reputation: 1
    New Member
     
    #7

    Jan 30, 2006, 07:53 PM
    Quote Originally Posted by czombos47
    Ok. I can turn the thermostat to 72 and it will stay on 64 with the fan blowing constant. Burners aren't firing. On the control board for the furnace, there is a trouble shooting light that blinks to tell you what is wrong. It blinks four times which indicates an "Open Limit Switch", and it tells to check the "main limit open", or the aux limit open". Well, where are those and is this gonna b tough and expensive?
    You will find the limit switch near the burners... it has two wires
    Going to it. There should be a red button sticking up... just press
    It in... there may also be others like in the burner cabinet.. or it
    Could be a bad fan relay.. that is a also a switch with two and
    Sometimes three wires going to it. It is mounted on the wall on the burner cabinet. It is about 2" BY 3". Try jumping those wire out
    By putting a wire between the two wires.. if your burner lights,
    There is your problem. Get a new one from any goodman supplier
    Asap. Good luck
    rescher's Avatar
    rescher Posts: 1, Reputation: 1
    New Member
     
    #8

    Dec 6, 2010, 09:46 AM
    I have a goodman, GMP Series Furnace and it is only clicking. Any suggestions

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman furnace problems [ 21 Answers ]

Hi - I have a Goodman GPM furnace. It works intermittently. I replaced breaker, thermostat, Control board and surface igniter. All appears well on start up sequence ; blower runs and igniter heats up and then turns off as no gas comes out. Control board codes says OK. Can anybody recommend what to...

Poor Cooling - Goodman high efficiency [ 11 Answers ]

I have a two year old Goodman unit that does not cool properly. The suction line does not get cold - barely slightly cool. It is a 3-ton high efficiency unit with a 5-ton coil. The orifice size was changed from a 74 to a 73, which is now the recommended size. The pressures were 72 and 190 on a 90...

Gas furnace [ 14 Answers ]

Igot a 1972 carrer furnace it catches fire at the spud part of burner I got 11.5 inch watter column preasure on line you can cut it off turn it back on and it burns good blaze looks good I need some comet on air ajustment or what might be causing this I have cleaned the burners , thanks.

Goodman Model A32-15 [ 1 Answers ]

I understand how ot wire abasic thermostat but on my Goodman I have OTC-OT1-OT2 & OT3. What are these for?


View more questions Search