    Goodman. 3 amp fuse on the board keeps burning out.
    I have a 9 year old 3 Ton Goodman central heating and cooling system. The furnace is horizontal Goodman and is located in the attic. Last summer I had replaced the fan motor, compositor on the condenser. The whole system shuts off after a night of use. The first time I discovered the burned fuse and replaced it. After another days use the same thing has happened. I called a local Tech and he came over and replaced the fuse again and changed the filter, stating he couldn’t find anything else wrong with the unit. I was told by the tech that it could be because I had a dirty return filter, and that would cause the problem. I think this is a wiring problem but he couldn’t find any breaks in the wires. Also he suggested he chemical washes the coil because it’s very dirty. After a nights use on auto/cool, the fuse on the board burns out. Any suggestions?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Sep 26, 2008, 04:49 PM
    After a nights use on auto/cool, the fuse on the board burns out. Any suggestions

    You have a intermittent problem. Could be low voltage wires that have rubbed through somewhere. I do not believe a chemical wash is going to fix this problem so forget that until the low voltage electric problem is solved.

    You will need a good ON SITE service person to figure this one out. There are items called tattle tails and other devices that a professional can use to help determine the cause of the problem.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #3

    Sep 26, 2008, 05:02 PM

    hvac1000 is right on. This is definitely a low voltage problem, if in fact the fuse that blows is on the control board. If it's a three amp, then I would say it is. But please let me know where exactly the fuse is located.
    HYE's Avatar
    HYE Posts: 2, Reputation: 1
    New Member
     
    #4

    Sep 26, 2008, 11:01 PM
    Quote Originally Posted by mygirlsdad77 View Post
    hvac1000 is right on. this is definately a low voltage problem, if in fact the fuse that blows is on the control board. If its a three amp, then i would say it is. But please let me know where exactly the fuse is located.
    The fuse is on the board.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #5

    Sep 26, 2008, 11:21 PM

    Knowing if it only happens on cool would help.

    The first thing to do in a case like this is to manually inspect the tsat, heater and outside unit connections and examine the wire where you can.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

3-amp fuse on circuit board [ 7 Answers ]

I've been having an intermittant problem where the 3-amp fuse on the circuit board keeps burning out. Lately, the problem has occurred in the late afternoon (3-7pm) such that when I replace the fuse, it will last for 3-4 minutes before blowing again. If I wait until late in the evening to turn on...

Goodman force air fuse blown [ 6 Answers ]

My force air unit is manufactured from Goodman (Model CKL30-1L). The controller is on the attic. The fuses do not blow when it is switched to heat and the unit runs fine. However, when switching to A/C, all the fuses blow. Please advise for the problem.

Fuse getting blown on Goodman logic board [ 4 Answers ]

I've Goodman forced air heating and Goodman A/C (compressor). The moment I put A/C on the 3A fuse blows on the circuit board which in the blower compartment of the furnace. Heat and blower work fine. Earlier nothing was working, it took a long time for me to narrow down the problem of fusing...

Goodman controller board fuse blows [ 8 Answers ]

I have a Goodman GMPN120-5, service guy replaced PCB in Aug due to A/C failure, root cause unkknown or not documented. Last week I turned on heat for first time this season, now nothing runs. Service guy returned, located blown 3A PCB fuse, replaced, still blows. Replaced fuse with 5A for testing...


View more questions Search