    Gas furnace
    Gas furnace made roger white 505a-241 contaroller flash 3 times error code that means pressure switch stuck open. I don't know and where is the pressur switch. Please help.



    Thanks
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Jan 12, 2007, 11:51 PM
    Find the small blower that pulls combustion air through the heat exchanger. The pressure switch, or at least the hose leading to, it will be between the blower and the heat exchanger. It will have a couple of wires leading to the control board. They may have numbers on them you can check on the schematic.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #3

    Jan 13, 2007, 03:49 PM
    Turn the main power off going to the furnace and then back on this will reset the control board. Turn thermostat back on and see if it works. If not take a screwdriver handel end tap lightly on the round pancake looking part above the burners. (two or three wires and a rubber hose will conect to this part). Good luck.
    KidChaos's Avatar
    KidChaos Posts: 45, Reputation: 3
    Junior Member
     
    #4

    Sep 29, 2013, 03:24 AM
    The tubing to the induced draft proving switch is attached to a barbed port on the inducer motor assembly, this port clogs requiring clearing.
    Try this, call for heat and after the induced draft motor starts jumper the pressure switched leads together, the ignition should begin, if so your ignition and gas valve are OK it's the port or less often the switch is defective. But clear the port or you will replace the switch to no gain. A clogged furnace condensate drain can do this too.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Gas Stoves connection to gas line [ 2 Answers ]

I had a serviceman connect my gas stove/range back up to the gas line. When I asked him if he used teflon tape or liquid pipe dope he said neither as my compression fittings was a type that did not need it. I was not aware there was such a compression fitting. The gas line does not appear to be...

Gas line to exterior gas lantern [ 1 Answers ]

I'm looking to run a gas line from the main gas supply of my home, to a gas lantern about 140 ft away. The line will need to be buried in the ground and will have to pass underneath my driveway. I believe there is a flexible line with a trace wire that can be used. I want to do the majority of the...

Gas water heater & gas dryer [ 4 Answers ]

I just moved into an duplex and purchased a gas dryer in excellent condition from a local thrift store. My trouble is, I don't see anywhere to hook the gas line (from the dryer up). It looks like there is just an electrical outlet. Can someone help? Isn't there some kind of two prong gas line...

Fan doesn't come on for AC or furnce [ 1 Answers ]

I have a furnace that is about 14 years old, and a central air conditioning unit that is about seven years old. I noticed yesterday that, although the house was cool, the fan was not blowing. It will not blow when either the heat or the AC is on. I turned everything off. Please advise as to...


View more questions Search