Furnace won't ignite-blowing cold air
Hello all, GMP power vented gas furnace won't ignite-blower is blowing cold air-indicator light is flashing 4 times...
|
|
|
Ultra Member
|
|
Jan 6, 2009, 08:38 PM
|
|
Check service label for translation of LED fault code and post here. Look inside blower access panel. Continuous blower operation usually indicates an open limit device.
|
|
|
New Member
|
|
Jan 6, 2009, 09:06 PM
|
|
Originally Posted by KC13
Check service label for translation of LED fault code and post here. Look inside blower access panel. Continuous blower operation usually indicates an open limit device.
Does this mean that a limit switch needs to be replaced?
|
|
|
Plumbing Expert
|
|
Jan 6, 2009, 09:12 PM
|
|
Maybe. But it may be as simple as pushing a button on a flame rollout. Have you checked filters lately. There is most likely a reason for limit malfunction
|
|
|
Senior Member
|
|
Jan 6, 2009, 09:16 PM
|
|
The OP didn't state that the blower was running constantly, just that it was blowing cold. Could just be an ignition failure. Flame sensor perhaps. Need more information to accurately diagnose.
|
|
|
New Member
|
|
Jan 6, 2009, 09:51 PM
|
|
Originally Posted by mygirlsdad77
maybe. but it may be as simple as pushing a button on a flame rollout. Have you checked filters lately. There is most likely a reason for limit malfunction
I actually changed air filter about an hour before we noticed no heat coming out just continuous cold air-blower running non stop
|
|
|
Plumbing Expert
|
|
Jan 7, 2009, 07:04 PM
|
|
Just waiting to hear what the code means. You should be able to find it on inside furnace cover or in furnace manual.
|
|
|
Ultra Member
|
|
Jan 7, 2009, 07:11 PM
|
|
Originally Posted by rebelsinjin
I actually changed air filter about an hour before we noticed no heat coming out just continous cold air-blower running non stop
Was the heat working before you changed the filter?
|
|
|
Full Member
|
|
Jan 8, 2009, 12:00 PM
|
|
Your thermostat isn't set on "run" instead of "auto" is it.
Just had to ask
|
|
|
Senior Member
|
|
Jan 8, 2009, 05:49 PM
|
|
Originally Posted by cyberheater
Your thermostat isn't set on "run" instead of "auto" is it.
Just had to ask
You mean "ON" not "RUN"
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Furnace sometimes blowing cold air
[ 7 Answers ]
We bought a brand-new house in May 2002. This winter (I don't think it happened last winter) when it got really cold outside, the furnace blew cold air. When it warms up outside, it starts blowing warm again. We had someone come and look at it and he told us it had a 30 degree heat pump?? And when...
Furnace blowing cold air.starts out warm, goes to cold.
[ 6 Answers ]
Hoping for help here. I recently had my ignitor replaced. Before that, the furnace wasn't working at all. Now it starts blowing warm (not hot) air, then gradually over a period of a couple of hours, the air cools down until it is completely cold and the temperature in the house drops drastically....
Furnace blowing cold air!
[ 2 Answers ]
i have been experiancing problems with my furnace blowing out cold air, the first time i checked the code light it was working normal, the second time it was flashing continuosly fast and it meant call for heat, the third time i checked it said to replace the IFC!! i have no idea what the ifc is,...
View more questions
Search
|