    davidwi5777's Avatar
    davidwi5777 Posts: 5, Reputation: 1
    New Member
     
    #1

    Nov 10, 2009, 07:37 PM
    Furnace not working
    I have a nordyne furnace in a doublewide. I replaced the 8" plastic piece below the vent pipe because one of the two fans was not working. Now after putting the new unit in it does not work? What did I do wrong?
    EPMiller's Avatar
    EPMiller Posts: 624, Reputation: 37
    Senior Member
     
    #2

    Nov 10, 2009, 08:03 PM

    Need more clearly described information to be of much help here.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #3

    Nov 10, 2009, 08:07 PM
    Does not work... be more specific.
    davidwi5777's Avatar
    davidwi5777 Posts: 5, Reputation: 1
    New Member
     
    #4

    Nov 10, 2009, 08:13 PM
    Quote Originally Posted by EPMiller View Post
    Need more clearly described information to be of much help here.
    The red light is blinking two times. This means there is a pressure switch problem. I replaced the bad fan unit, but the new one does not work.
    davidwi5777's Avatar
    davidwi5777 Posts: 5, Reputation: 1
    New Member
     
    #5

    Nov 10, 2009, 08:15 PM
    Quote Originally Posted by davidwi5777 View Post
    The red light is blinking two times. This means there is a pressure switch problem. I replaced the bad fan unit, but the new one does not work.
    Is there a reset button I should push?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #6

    Nov 10, 2009, 08:25 PM
    If the inducer isn't running, the pressure switch will not engage. Is the motor wired correctly? Why was it replaced? Is it being powered?
    davidwi5777's Avatar
    davidwi5777 Posts: 5, Reputation: 1
    New Member
     
    #7

    Nov 11, 2009, 06:45 AM
    Quote Originally Posted by KC13 View Post
    If the inducer isn't running, the pressure switch will not engage. Is the motor wired correctly? Why was it replaced? Is it being powered?
    The inducer was replaced. That is the motor I was referring to . It was replaced because one of the fans was not turning. I put the new inducer in and the light still blinks 2 times which means the pressure switch is open. I am stuck.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #8

    Nov 11, 2009, 04:09 PM
    Is the pressure switch hose connected to the new inducer in the same fashion as it was to the old one? Use a straightened paper clip to check the hose connection port on the new inducer for blockage. Also, try this: set thermostat to demand heat. Using a vacuum cleaner with a hose attachment, hold the end of the pressure switch hose near the end of the vacuum cleaner hose (don't seal them together!). See if unit starts heating. If it does, you may have a leaky seal where the inducer mounts.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace & AC Not Working [ 0 Answers ]

Having a problem with my AC/Furnace. AC was working fine and was turned on for about 3 weeks. Thursday night it cooled off and we opened up until Saturday morning. On Saturday morning the AC would not turn on, neither would the furnace side. Furnace is a Janitrol GMP100-4, 14 yrs old. Checked...

Dual fuel rheem furnace not working, defrost control board replaced still not working [ 1 Answers ]

Hello there, I have a Rheem furnace and is only one year old. Recently my furnace didn't come on so I had someone come out and look at it and it turns out it was the defrost board on the heat pump that was bad. I replaced the board with a new one and turned the system on and it worked on heat and...

Furnace burner keeps working even if the blower is not working [ 3 Answers ]

My gas furnace (Trane XL80) this morning started to smell like plastic was burning from the registers, I went to check the furnace and noticed that the blower wasn't working so I turned the breaker off. My question is, should the burner had to turned off if the blower wasn't working for some time?

Furnace not working [ 2 Answers ]

I have a payne HVAC and burner will come on, when I went up in the attic to check it out I noticed a part missing, I believe it was the alternate limit switch, would this cause for the unit to not come on, do I need a switch? Thanks in advance to whom ever can answer my question!

Furnace not working! Help! [ 4 Answers ]

We have a Montgomery Ward 700 furnace with central air. It worked fine all summer. My husband turned the heat on about two weeks ago and all was well. A couple of days ago it started to act up. It would kick on and the blower would come on and kick off in a few seconds. Every three or four minutes...


View more questions Search