    Furnace fan only runs for 30 seconds
    I have a gas furnace in our home. Recently the furnace gas preheats and the fan comes on but only will run for 30 seconds, when the gas reignites the fan turns off. I changed the filter but that made no difference. I looked at the fuses and while looking discovered the that the hot and common wire marrets had melted. I respliced and reconnected the wires but this has not made a difference either... this morning I tried putting an old style mercury switched thermostat in place but the system still runs the same... has something blown on the circuit board and if so what am I looking for??

    Dumbfounded
    eeseely's Avatar
    eeseely Posts: 100, Reputation: 3
    Junior Member
     
    #2

    Jan 29, 2008, 03:45 PM
    I had the same problem with my propane furnace.
    The problem was that water is a product of combustion, and
    It was not draining out of the burner area, properly---due to the
    Little drain hose's being frozen.
    What brand of furnace do you have?
    melamar's Avatar
    melamar Posts: 3, Reputation: 1
    New Member
     
    #3

    Jan 29, 2008, 03:58 PM
    Quote Originally Posted by eeseely
    I had the same problem with my propane furnace.
    The problem was that water is a product of combustion, and
    it was not draining out of the burner area, properly---due to the
    little drain hose's being frozen.
    What brand of furnace do you have?

    This is a Bryant furnace, model 394GAD036100... there aren't any drain hoses on this model that I can see?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Jan 29, 2008, 04:43 PM
    If the unit only runs for 30 seconds or so and you have a flame sensor try cleaning it.

    If you have a 3 wire pilot system check the height of the pilot flame.
    melamar's Avatar
    melamar Posts: 3, Reputation: 1
    New Member
     
    #5

    Jan 29, 2008, 07:54 PM
    Quote Originally Posted by hvac1000
    if the unit only runs for 30 seconds or so and you have a flame sensor try cleaning it.

    If you have a 3 wire pilot system check the height of the pilot flame.

    I cannot find a flame sensor that looks like a pencil tip. What I do find is a 2 wire sensor type that is just above the burners, it extends inward to the cavity about 3 inches and has a round sensor type on the end. I tried the system again and what it does is this: the system ignites immediately but continues on a long burn(2-3 minutes) before the fan kicks in. At this point the burner shuts off, but as soon as the burner reignites the fan kicks out and a long burn continues?? any ideas?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Jan 29, 2008, 09:51 PM
    It is possible the flame is being dropped out by the high limit switch. You may need to adjust the fan control to come on sooner so the heat does not build up in the furnace and kick the high limit into action. See sticky notes at the beginning of this board for location and a picture of a fan/limit control.

    Being a Bryant this control might be a fixed disc and in that case you would have to test it or just replace.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Coleman electric furnace fan runs only in manual [ 2 Answers ]

I have a mobile with a forced air Coleman electric heat. The fan will not run in the auto setting (switch by motor in cabinet) but the element will heat up. In manual the fan runs constantly and heat comes on with the thermostat. The heating company recently replaced the sequencers and said we...

Lennox furnace fan runs on forever [ 1 Answers ]

I have a 10 year old Lennox conservator II forced hot air gas furnace, the furnace itself runs good and produces heat , the problem I have is that the furnace cycle never ends it turns on produces heat then the firing stops the fan continues to run it cools down then before the fan cycle stops...

AC fan runs slow, but switch to heat fan runs normal [ 3 Answers ]

The other morning I came into the house and noticed the ac was not working. I turned off the breaker to the unit for a few minutes. Then turned it back on. Went to the thermostat pushed it over to auto and the fan came on but ran very slow. I them turned it off. Then turn on the heat, the fan...

1990 Eagle Talon starts, runs 2 seconds, dies. [ 3 Answers ]

My 1990 Eagle Talon turbo AWD starts, runs about 2 seconds, then dies. It just started doing this when I took the ECM out from under the dash to look at the wiring. Sometimes by wiggling the wires around I can get it to run normally (not die). Then while it is running, if I wiggle the wires...

Inside fan runs, outside fan runs, but air is not cold [ 8 Answers ]

The inside fan runs and runs, the outside fan on the compressor runs and runs, but only hot air comes out. I sprayed the outside compressor coils with the garden hose to clean them and checked the inside filter. Is there something else I could check? Thanks


View more questions Search