    Furnace blowing cool air
    I have a Trane XL80 furnace, the past couple weeks I have had blower running but no heat. System shows 2 flashes: System Lockout (No flame) check line polarity.
    If I shut off switch (by fuse) then turn back on, it will ignite (but might take a couple ignites, if after 5 X's and burners do not stay lit, it will lockout again. The burners will light for 3 - 10 seconds then go out. Any suggestions on cause?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Mar 22, 2008, 11:33 AM
    If you have a flame sensor clean it or replace.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #3

    Mar 22, 2008, 07:48 PM
    I agree start with cleaning the flame sensor. If all the burners are not lighting or slow to light it will give you the same code also. The only time you need to replace the flame sensor is if you broke the metal rod off or if the ceramic is broke or cracked on it.
    PITTPSU's Avatar
    PITTPSU Posts: 3, Reputation: 1
    New Member
     
    #4

    Mar 23, 2008, 05:05 AM
    Quote Originally Posted by hvac1000
    If you have a flame sensor clean it or replace.
    I removed sensor, cleaned with scotchbrite pad, replaced. 1st ignition stayed on.
    So far, so good. Thanks!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Mar 23, 2008, 06:08 AM
    Glad you got it fixed.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace barely blowing cool air [ 4 Answers ]

Hi,I have a concord 80 plus furnace installed in 2002... Everything is kicking on the fan turns on, the igniter ignites the gas , and a minute or so later the blower comes on... problem is the air is cool and barely blowing?? all vents are open correctly... cold air return is working fine... filter...

Furnace blowing cool air [ 2 Answers ]

A Goodman furnace was recently installed in the flat that I rent. The problem is it is going on and off 24/7 and during it's cycle it goes like this: furnace starts up for about 20 seconds, the gas jets ignite for another 20 seconds, then blower turns on and begins to first blow cool air for...

Furnace is shutting off early and still blowing cool air. [ 4 Answers ]

Hello, I have a Trane XE80 (14 years old) that periodically shuts the gas off but the blower continues to blow trying to heat the house up. If I shut the furnace off, allow it to restart, everything will work fine for a few hours or days. So the occurrence is random. Some background info. ...

Furnace blowing cool air [ 3 Answers ]

I have a Bryant gas furnace. About 2 days ago it was working fine. Yesterday I noticed it was very cool in my house. I checked the vents and they were blowing cool air. The fan stays on continuously. The pilot is lit and the filter is new. What are some possible causes and solutions to this...


View more questions Search