    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #1

    Jan 3, 2008, 10:44 PM
    Diagnostic Light is off and Blower does not come on
    I have a Bryant 373LAV/376CAV (not sure exactly which one) mounted horizontally in the attic that is <5 years old and has been functioning perfectly since installed. However, because Houston doesn't get very cold winters and this furnace serves the second floor, which we rarely use, I am not sure how long the heater has not worked.

    This evening when we had guests over I noticed that the upstairs was cold and heater was not coming on. Initially, there was a 31 error code flashing and when I power off the unit and power up, I get the normal 90 second main blower operation (and the '12' error code indicating 90 second power-on blower), followed immediately by a shutdown and nothing else. I tried to eliminate the thermostat from being the problem by removing the red and white wires from the furnace, to no avail.

    Now, the diagnostic light is completely off and nothing comes on when the unit is powered off/on. Any thoughts on what I can try next?

    Thanks...
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Jan 4, 2008, 05:28 AM
    Sounds like you blew the low voltage fuse working on it. See https://www.askmehelpdesk.com/heatin...ons-58313.html

    Once you fix the fuse, check the inducer and its pressure switch. If the pressure switch doesn't signal the inducer blower is going, it shuts down.
    therinnaiguy's Avatar
    therinnaiguy Posts: 153, Reputation: 5
    Junior Member
     
    #3

    Jan 4, 2008, 07:18 AM
    Check the door safety switch. The access panel may be out of position not allowing the system to operate. Follow labman's recommendations.
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #4

    Jan 4, 2008, 11:52 AM
    Thank you for the prompt responses! I checked the door safety switch and it looks to be working properly. I replaced the fuse and diagnostic light is back on. 31 is still flashing. Checked pressure switch but didn't see anything out of the ordinary. Will replace pressure switch and let you know outcome. Please advise if I should try something else in the menatime. Thanks again!
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #5

    Jan 4, 2008, 04:02 PM
    I've replaced the pressure switch. Fan comes on for 90 seconds then it sounds like the burners come on for about 10-15 seconds then furnace shuts down. Diagnostic code is now 21. Did I mis-wire the switch?

    Thanks...
    Tarey Wolf's Avatar
    Tarey Wolf Posts: 6, Reputation: 1
    New Member
     
    #6

    Jan 4, 2008, 04:20 PM
    Quote Originally Posted by carpet1
    Thank you for the prompt responses! I checked the door safety switch and it looks to be working properly. I replaced the fuse and diagnostic light is back on. 31 is still flashing. Checked pressure switch but didn't see anything out of the ordinary. Will replace pressure switch and let you know outcome. Please advise if I should try something else in the menatime. Thanks again!
    I have the same unit... with perhaps the same problem. Where is the fuse in this unit? Is it the "fusable link" picture in the referenced link? Thanks.
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #7

    Jan 4, 2008, 04:49 PM
    On my furnace, 3 Amp fuse is on the mother board, to the left of the diagnostic light. Good luck...
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #8

    Jan 4, 2008, 04:49 PM
    I was able to clear error code 21 by turning the gas valve off for 5 minutes and turning it back on. Error code 31 is now on display again. Pressure switch has been replaced. Any thoughts on what I should do next? Thanks...
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #9

    Jan 4, 2008, 05:51 PM
    If the burners come on and go off in a few seconds, usually it is a dirty flame sensor. Pictures of them in the sticky. A few minutes with fine sand paper and the furnace should be running. Note, there should be a decal giving the codes.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #10

    Jan 4, 2008, 06:12 PM
    The inducer motor has to be running to close the pressure switch. Not sure about code 32 but code 23 is the pressure switch did not open on shut down. Blow and suck lightly on the tubes going to the pressure switch, you should hear it click. Make sure the collector box is not obstructed with rust at opposite end of tube. TURN POWER OFF FIRST. Code 12 is the thermostat was calling for heat when you turn power back on to the system the blower runs for 90 sec.
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #11

    Jan 5, 2008, 03:39 PM
    OK. Here's the latest on my saga... Initial problem was error code 31 on my Briant 373LA horizontal furnace. After replacing pressure switch, burners fan would run for ~90 sec. the inducer, or what I think is the inducer, would start spinning, the burners would come on and then shutdown after 5 seconds or so. Diagnostic code now reads 21. Sanded the flame sensor, to no avail; same results as presviously.
    The definition I found for error 21 is: "Gas Heating Lockout - Control will NOT auto reset. Check for stuck gas valve relay on control or miswire to valve circuit." The only rewiring I've done was disconnecting and reconnecting to the pressure switch.
    What do you suggest I try next? How do I check for stuck gas valve relay (if that's really the problem)? Could I have the pressure switch wires reversed? Don't think it'd be working this far it that were the problem. Thanks for your patience with my problem.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #12

    Jan 5, 2008, 05:06 PM
    Make sure gas valve is in the on position and that the gas is on going to the furnace. Make sure you did'nt pull a wire loose when messing with the pressure switch. The gas valve has a ground wire on the common side of the coil it has to be grounded to the equipment to work(green wire with yellow tracer).
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #13

    Jan 6, 2008, 05:47 PM
    Thanks... Made sure gas valve is in the ON position on gas line and furnace; all wires, including ground, are connected properly. Same symptoms; solid diagnostic light initially, fan comes on for 90 secs or so, inducer starts spinning, orange flame comes on behind burners, leading me to believe burners light up, for 5 seconds then furnace shuts down and error code 21, listed above, starts flashing. Please advise...
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #14

    Jan 6, 2008, 06:24 PM
    Make sure the flame sensor is not touching any metal(if ceramic around flame sensor is cracked it can go to ground and not work), check to see if flame sensor wire is not grounded,damaged or loose. If the burners light up its not a bad gas valve. Are you using L.P gas or natural gas?
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #15

    Jan 7, 2008, 08:24 AM
    Thanks T-Top. Will check sensor. Am using natural gas. This is one of two furnaces in the house and the other is working fine...
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #16

    Jan 7, 2008, 08:08 PM
    Well, I checked sensor and it's free from any contact; however, I did find that the wire connected to it was loose, so I tightened it (must have come loose when I removed sensor to sand it down). Anyway, the error code now displayed is 31 again, and the burners will not come on and the inducer motor will not spin. Before, when error 21 was being displayed, the burners would come on for a few seconds. I have to believe that the inducer motor works fine because it was spinning when the burners would light up. I'm at a loss! I've been asked to check the inducer before to try to correct error 31; what specifically am I looking for? Do I need to test the capacitor? If so, how? Thanks again.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #17

    Jan 7, 2008, 08:47 PM
    If the inducer runs, the capacitor is fine. Check the hose and wires to the pressure switch.
    carpet1's Avatar
    carpet1 Posts: 13, Reputation: 1
    New Member
     
    #18

    Jan 8, 2008, 05:19 PM
    I've checked the two wires on the pressure switch and connections look good. The hose seems to be OK as well. It's at eye level with pressure switch and there are no kinks in it. 31 still flashes. Anything else I should try? I'm no expert, as evidenced by this log of entries, but it's surprising that any one part is deffective when they randomly work, switching from error 21 to 31. Anyway, please let me know if there's any part you think needs replacement.
    Frdbrkl's Avatar
    Frdbrkl Posts: 94, Reputation: 7
    Junior Member
     
    #19

    Jan 12, 2008, 05:52 AM
    The pressure switch diagnostic simply tells you the pressure switch is not opening/closing properly. Most often, that means something is *preventing* it's operation-not a bad switch!

    Check the intake to the burner compartment for leaves-most common problem. Disconnect the PVC pipe going to the burner compartment, move it aside, and check inside with a flashlight. Remove any leaves, debris from intake (clean it up GOOD) and reinstall. If you found a bunch of leaves-this was undoubtedly the problem.

    If you've cleaned the intake and still have the error, then start looking at the condensate drains. A clogged condensate discharge trap (small white box with rubber hoses connected to it-it's in the blower compartment of most) will also prevent the pressure switch from opening sometimes. Blow through ALL of the ports on the trap to clear it, put it back together. You should be in operation by this time.

    Hope this helps.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #20

    Jan 12, 2008, 03:20 PM
    It only takes a very small restriction in the vent pipe to keep the pressure switch from closing.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Anyone know the diagnostic codes for a goodman furnace? [ 3 Answers ]

Hi, I have an older model goodman furnace that powers up the vent fan and proceeds far enough in the sequence for the electric igniter to glow, but then never releases gas to complete ignition. I replaced the gas valve last year, so I am hoping it isn't this again. I am getting an error code on the...

HVAC Diagnostic steps [ 14 Answers ]

I have a 10 yo White and Rogers system in the attic that this year decided not to start. Last year its sister unit in the basement did the same and a new control unit fixed it (but we chalked that up to sitting in water for several years). Now, when heat is called for, the attic draft inducer...

Furnace diagnostic code [ 1 Answers ]

Concord furnace diagnostics : 3 flashes : Pressure switch is open while inducer is on.