Day & Night furnace blower runs every minute
The Day and Night furnace air blower runs for 20 seconds every minute. This happens even when the thermostat is completely disconnected. The only way to stop this is to unplug unit for several hours( 3-6 ) then it will operate normally for 6-8 hours before starting the blower every minute. Any ideas?
|
|
|
Ultra Member
|
|
May 19, 2007, 09:10 PM
|
|
What is the model of the furnace?
|
|
|
Heating & Air Conditioning Expert
|
|
May 19, 2007, 11:50 PM
|
|
I believe you will be replacing the circuit board unless it has a separate motor timer device. If it is a newer model with a DC motor hold on to your hat when you get the price.
|
|
|
New Member
|
|
May 20, 2007, 07:23 AM
|
|
Model # is: 398AAV036040A
Product # is: 398AAV036040AAKA
Blower motor is 120 VAC
|
|
|
Ultra Member
|
|
May 20, 2007, 08:01 AM
|
|
I agree with hvac1000, I'd say it's a bad blower relay on the control board.
|
|
|
New Member
|
|
May 20, 2007, 09:16 AM
|
|
Do you need to replace the control board or can you just replace the relay?
|
|
|
Heating & Air Conditioning Expert
|
|
May 20, 2007, 09:37 AM
|
|
More than likely the relay is part of the board. You will have to look on your furnace for the wiring diagram.
|
|
|
Ultra Member
|
|
May 20, 2007, 09:47 AM
|
|
What brand is the furnace? I'm not familiar with that model number.
|
|
|
New Member
|
|
May 20, 2007, 10:23 AM
|
|
Okay, I have the control board in my hands. The blower relay is part of the circuit board. Looks like I would need to use a soldering iron to remove Now can you guys tell me where I can get a new board? I would call a tech in, however, where I live (far north Sonoma coast of California) it very difficult to get services up here. By the way thanks very much for your help.
|
|
|
Heating & Air Conditioning Expert
|
|
May 20, 2007, 11:39 AM
|
|
|
|
|
Ultra Member
|
|
May 20, 2007, 04:33 PM
|
|
Check all your limit switches first. If you have a bad spade or wire connection going to a limit switch it will do what your saying. If the 24 volt circuit is broke at any time heating or cooling the blower will run. Sounds like a loose 24 volt wire connection to me.
|
|
|
Junior Member
|
|
Apr 13, 2008, 03:10 PM
|
|
This is what is wrong with your unit it is old and the old it gets the more time you use it so get a NEW UNIT That's ENVIROMENTLY Friendly
|
|
Question Tools |
Search this Question |
|
|
Add your answer here.
Check out some similar questions!
Fan blower runs on and off all day
[ 1 Answers ]
Why does the fan blower run on and off all day? How can I turn it off and save energy and the fan blower motor from burning out? Please help
Thank you
Day & night not igniting
[ 1 Answers ]
I have a Day & night furnace and I can't get it to lite. It has a lockout module and the wiring is messed up. I need to know how this system works, how does it lite and what makes the blower go on after the burner lites
Day & night creams?
[ 1 Answers ]
Have you found any that are really good? I recently tried Avon and it was very smelly once on. Any suggestions?
My furnace runs all day
[ 3 Answers ]
The burners fire for a minute or two at most then turn off for a minute or two. This repeats all day and it won't get above 64f in the house.
View more questions
Search
|