    turtle01355's Avatar
    turtle01355 Posts: 1, Reputation: 1
    New Member
     
    #1

    Apr 24, 2008, 04:32 PM
    Condensing unit not working
    I wanted to know why the contactor is not closing to start the compressor and outdoor fan motor, my indoor fan is coming on.
    twinkiedooter's Avatar
    twinkiedooter Posts: 12,172, Reputation: 1054
    Uber Member
     
    #2

    Apr 24, 2008, 04:49 PM
    Because it needs replaced.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #3

    Apr 24, 2008, 06:18 PM
    We need more info if you can give it. Is it a heatpump or just a/c, how old is it 10, 15, 20 years old? Some of the systems use pressure switches and time delay relays that 24v has to pass through before the contactor.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #4

    Apr 25, 2008, 07:29 AM
    If the contactor is not closing,, are you sure the low voltage (24volts ) is going to contactor to turn it on or kick it in,, can you push it in manually with a srewwdriver and allow it to kick back out by itself,, or test with a meter for 24 volt power
    jamol's Avatar
    jamol Posts: 1, Reputation: 1
    New Member
     
    #5

    Aug 14, 2010, 07:22 PM
    Quote Originally Posted by T-Top View Post
    We need more info if you can give it. Is it a heatpump or just a/c, how old is it 10, 15, 20 years old? Some of the systems use pressure switches and time delay relays that 24v has to pass thru before the contactor.
    I can push it in with a screwdriver and compressor and fan run
    PellMell's Avatar
    PellMell Posts: 33, Reputation: 3
    Junior Member
     
    #6

    Aug 14, 2010, 08:38 PM

    Is it a heat pump? Check the voltage on the (normally) yellow wire. It should be 24 VAC. If it is not approximately that value, check to see if you have a float switch. If the float switch is activated or defective, the outside unit on a split system will not kick in.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Lennox AC13 condensing unit [ 1 Answers ]

I have a Lennox AC13 condensing unit that comes on and then cuts off. It will not stay on

Central AC condensing unit not coming on [ 5 Answers ]

I just bought a house with Central AC. I tested the unit initially and it worked fine. I just turned it on and the outside condensing unit is not coming on. I went out to look, and I see a white wire that is taped to the insulated pipe coming out of the house, and the wire goes to nothing - just...

Leaks a/c condensing unit [ 1 Answers ]

There is no charge in my system, it leaked out. I don't have a vaccuum pump, how can I remove the air, could I run some r-22 through the system to chase the air? If so how can I do this. Do the scharder valve o-rings go bad? If so where can I buy them

Condensing unit not coming on [ 8 Answers ]

Hi I have an Amana system that is maybe 15 years old. I can find out if anyone needs to know but I'm at work now so that will have to wait. Anyway, I have noticed that the cold air is not so cold anymore. The past few days that cold air problem has been compounded by the condensing unit not...

New condensing unit problem [ 1 Answers ]

I installed a new condensing unit and put freon in the unit, I am getting the same pressure on the high and low sides of the gauges. This leads me to believe that there is a compressor problem or that I put too much gas in it. I am reading 150 psi on the high side and the gauge is pinned on the low...


View more questions Search