    Compressor Runs-Blower motod doesn't
    Wondering if there was a way to troubleshoot fan relay and blower motor thermal protect to tell if either of these were thr cause of my problem. Thanks
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Aug 1, 2009, 01:12 PM
    fan relay

    If it is a stand alone relay then you can apply 24 volts to the proper terminals and see if the contacts close to activate the blower circuit.

    If the relay is on a circuit board then you will be replacing the board.

    motor thermal protect

    In almost all residential cases the blower motor thermal protection system is built into the motor winding circuit. While you could not test this item without tearing the motor apart you can use a Amprobe to check the running amps of the motor and if lower than the motors rating and it goes off on the thermal protector in the motor then the thermal overload circuit is defective, the capacitor is bad or the voltage is improper. The motor will have to be replaced or you might find a rebuilder to repair it.

    NOTE: While the above holds true for residential HVAC motor work commercial/industrial plays by a different game in many cases. Motor starters used by larger equipment will usually have heaters installed in them. When too much current is drawn the heaters will activate and drop the starter switch out of the circuit there by protecting the motor. This is just one example of many different ways protection can be done.

    Class is over for today.
    Attached Images
     
    Blondievm's Avatar
    Blondievm Posts: 2, Reputation: 1
    New Member
     
    #3

    Feb 5, 2013, 02:00 AM
    Compressor and motor blower work Ignites the stops flashes4 times replaces thermal protector still problem.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

AC Comes on, blower stops, compressor still runs [ 7 Answers ]

Whe I turned on the AC for the first time this spring, it started and ran normal for about 10 minutes. Then the HVAC blower stopped but everything (condenser fan and compressor) keeps on running. I turned the unit off at the t-stat waited five minutes and tried again - same thing. The blower...

Blower runs only 2 minutes but A/C compressor keeps running [ 1 Answers ]

The blower which pushes either cold air through the house as part of the central air conditioning only runs for about 2 to 3 minutes at a time. Then it shuts off. The Lennox compressor unit outside though, runs continuously. After a while (about 10-15 minutes) the blower turns on again. Is it...

Trane XE80 compressor runs, no blower [ 1 Answers ]

I have an approximately ten-year old Trane XE80 HVAC in the attic above the second floor of my house (cools and heats the 2nd floor). It does not operate properly--yesterday and last night, the blower would not come on in response to the thermostat. The outside compressor unit runs when the...

Running blower at slow speed all the time, and high when compressor runs. [ 1 Answers ]

I have a Carrier 58PAV090 furnace air handler. The fan has multiple leads which are used to run the blower at different speeds. The black is for High speed, yellow for medium high, blue for medium low and red for low. In the cooling mode, the blower turns on when the thermostat calls for cooling...

Cooling: blower runs but compressor does not start [ 3 Answers ]

I have a heat pump outside and a blower in the attic. Both made by YORK. My system stopped cooling a week ago. The blower keeps running but the heat pump does not start. I checked the circuit breaker in the basement and the power disconnect next to the outdoor unit. Both are good. I studied...


View more questions Search