    Compressor and fan not running
    After replacing a blown running capicitor on the outdoor unit I have power to the contactor but the unit won't come on when the thermostat calls for cooling. I can manually engage the contactor and the fan and compressor come on. I had no meter to check the power to the coil so I plan to do that next and assume a bad coil if power is there. If not then I assume either the thermostat or the 24v transformer. Am I missing anything?
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #2

    Aug 14, 2008, 07:00 PM
    Assumption will bite you on the butt every time. Is the blower motor running when you make the thermostat call for cooling or if you turn the fan switch to on ? If so its not the transformer. Make sure you did not knock a low voltage wire loose while replacing the run capacitor. If it's a rheem heat pump reset the high pressure switch.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #3

    Aug 14, 2008, 09:19 PM
    Yep, sounds like low voltage prob. The broken or loose wire trick can cause a lot of headaches,,
    jbrinlee's Avatar
    jbrinlee Posts: 2, Reputation: 1
    New Member
     
    #4

    Aug 14, 2008, 09:28 PM
    Quote Originally Posted by T-Top
    assumption will bite you on the butt every time. Is the blower motor running when you make the thermostat call for cooling or if you turn the fan switch to on ? If so its not the transformer. make sure you did not knock a low voltage wire loose while replacing the run capacitor. If its a rheem heat pump reset the high pressure switch.
    Yes, the blower motor runs both automatic and manual so transformer is out- thanks. It's an Amana RCC30C2A so I'm not sure about the high pressure switch. I guess it's down to a loose wire or a bad coil then?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Compressor Stops Running [ 1 Answers ]

The fan on my Tempstar outside unit slows after about 45 minutes of running, then comes to a complete stop. There is a smell as if something is hot. I have replaced the fan motor, capacitor and contactor with no change. Where do I go from here?

A C Compressor not running [ 2 Answers ]

I have a Carrier Model # 40AQ036330EH A/C, Heat pump unit installed in my home. I was working fine yesterday, but today the inside fan runs, but the outside unit is not running. I checked the main breakers in the garage and found one side tripped. I reset the breakers inside and outside with no...

Air conditioner compressor not running. [ 1 Answers ]

My air conditioner fan runs outside but the compressor does not come on. Why

Blower will not come on but compressor is running [ 5 Answers ]

I am having a problem with my a/c unit. I have had the HVAC people hear 7x and they can't seem to find the problem. They changed the thermostat thinking that was the problem but it only worked for about 3 hours after they did that. They said they were going to call the tech people with the mfg...

AC compressor not running [ 10 Answers ]

My AC froze up and stopped cooling. I turned the ac off, and put the fan in run mode until the ice melted. When I turned the unit back on, the compressor did not come on. It is an Amana, just over 3 yrs old. Bruce


View more questions Search