    Coleman evcon furnace doesn't work properly
    Coleman evcon model #bgm075166
    Here is process:
    I turn to temp with thermostat
    Furnace comes on and there's a click for the ignitor
    Ignitor glows then flame is started
    Ignitor clicks then turns off
    Then the flame cuts off shortly after the ignitor does
    The furnace then retries to ignite 2 times and fails and shuts down with 7 flash code which indicates "ignition lockout due to retries"

    At first I thought maybe house temp is just too warm for the furnace to start but it takes the house temp to drop a lot until it self-ignite
    When it does self-ignite it works fine and comes on properly
    Always seem to have this problem during late night ,early morning hours
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Nov 12, 2009, 04:10 AM
    Locate and clean the flame sensor. You will usually find it situated in front of the main burner OPPOSITE the ignitor, looks like a ceramic-insulated rod connected to a single wire. Use steel wool or fine sandpaper.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #3

    Nov 12, 2009, 06:02 AM
    My .02 cents worth
    Attached Images
      
    dragz's Avatar
    dragz Posts: 3, Reputation: 1
    New Member
     
    #4

    Nov 14, 2009, 04:49 AM
    Thanks a lot works like a charm now
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Nov 14, 2009, 08:53 AM
    Good deal.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Coleman evcon furnace [ 4 Answers ]

Furnace will won't heat. Model #BGMO7516B Serial # 980905038. Red light blinks once. Will ignite but won't kick in to heat.

Coleman evcon furnace [ 5 Answers ]

My home has coleman evcon furnace 12 years old.I can set the thermostat at 74 degrees and the furnace will start with a 30second purge then the ignitor will warm up and glow red then the main burner lights.then the burner stays lit and the blower runs for a couple minutes. Then the thermostat calls...

Coleman Evcon Furnace [ 1 Answers ]

We have a Coleman Evcon DLAS075BDD furnace which keeps displaying error codes: 1-Ignition Failure and 4-Limit cycling. We have replaced the circuit board. Inspected the ignitor and the flame sensor and both appear good. Also have taken the exhaust vent/hood off and vaccuumed out any rust to...

Coleman evcon oil furnace [ 8 Answers ]

I have an older coleman evcon oil furnace that ran fine until today.It still runs but the smoke exiting the chimney is pure black and sooty. Would this be an indication it's not getting enough air or maybe getting too much oil? Don't have any experience with oil furnaces. Thanks, Ken

Coleman evcon furnace [ 1 Answers ]

I have a coleman evcon direct vent forced air furnace, the air is blowing cool air, everythinig else is working it's firing ,the fan is working


View more questions Search