    Central heating header tank
    Upon restarting the central heating for the winter period the following 2 things have occurred (I don't think they're related)
    1) One of the rads only gets hot at the bottom (3/4 inches up the rad) the rad does not want to bleed i.e. no air coming out.
    2) AND MORE WORRYING ! - once or twice during the central heating period a huge amount of water spews out out of the overflow pipe from the header tank (only for about 20/30 seconds) then it's o.k. again. I have read previous answers on a similar theme i.e. a leak between the 2 systems but might have thought this would produce a small trickle rather than a large gush !

    Any help would be much appreciated.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Dec 8, 2006, 10:58 AM
    Pressure in the system is to high, should be 12 psi cold and about 18 hot, pressure relief valve lets go at 30 psi. Expansion tank could also be bad. Note, I see a lot of people going to Lowe's etc... and buying expansion tanks to do it them selves, these won't work since they are for domestic water and are pressurized too much.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Central Heating Radiator layout. [ 3 Answers ]

Hi, I'm going to be adding a new radiator to my CH System, but I can't find any one else with my sort of layout. And I can't fingure out how it works? Now I'm going to attach a drawing so you can see what I mean. There is just one pipe running in series around the house. I don't get what...

Central Heating Pump [ 4 Answers ]

How do I calculate the size of pump I need for my system

Gas Central Heating [ 1 Answers ]

When we switch on just the hot water control the hole system comes on i.e. (Hot water and heating together) and you cannot cotrol the temperature from the thermostat.

Drained central heating [ 1 Answers ]

I have drained my vented central heating system to clear sludge. The header tank has refilled but the system has not. I have removed the pump which was full of debris but there is no water coming out of the pipe from the header tank to the pump (a drop of eight feet). On loosening the compression...

Central Heating [ 8 Answers ]

Im not sure my central heating is working fine. I bought a new home and I have lived there about 2 yrs but I rarely used my central heating (long enough) over this time. Recently I used my central heating long enough (over 3 hrs) and noted that while the heating is good initially, the air looses...


View more questions Search