    vvkrolc's Avatar
    vvkrolc Posts: 1, Reputation: 1
    New Member
     
    #1

    May 22, 2007, 05:46 PM
    Central A/C outside runs but compressor kicks on and off
    Just cleaned the complete system, at furnace and outside. Had unit serviced (Sears Kenmore) for low freon, now when I turn on A/C the fan outside runs OK but the compressor kicks on then off after 10 seconds. This is the first time I ran the unit since it was serviced by a technician. Could this be a relay problem. The compressor won't stay on even though the line gets cold and hot air is blowing out from the fan. (the a/c guy said everything was running fine after he serviced it last week) Any suggestions, I hope it is not the compressor.

    Vince
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #2

    May 22, 2007, 07:59 PM
    If the compressor is coming on and staying for 30 seconds or so and then cutting off and the air coming out the top of the unit is hot and the suction line is hot, my guess is that you have an over load of freon. Did the service man charge you for freon and if so how much?
    The unit may have high and low pressure switches to protect the unit. Some do and some don't.
    Another possibility could be a very dirty outside coil.

    Rate this answer Please.
    hvacservicetech_07's Avatar
    hvacservicetech_07 Posts: 1,083, Reputation: 75
    Ultra Member
     
    #3

    May 22, 2007, 08:18 PM
    I would hope the service guy would have checked and cleaned the condenser coil while he was there. Does the condenser fan seem to be running at full speed? If so, I would have to agree that you either 1. have an overcharged system or 2. the freon has leaked out and the compressor is going out on low pressure. I would contact the service guy that checked the system ASAP to resolve this problem for this may be something he did, I would advise you to shut the system off until it's checked out or you may damage the compressor.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Central Air Compressor Wiring [ 4 Answers ]

My Compressor Quit Working A Few Months Back. The A/c/ Repair Guy Stripped The Burnt Wire On The Compressor And Added A New Wire It Worked Ok. I Called Another Company For My Yearly Service He Said The Wire Was Burn . He Pulled All Of The Wires Lose And Left. The Unit Is A Bryant That Says 1982...

Compressor on central air conditioner [ 6 Answers ]

The compressor on my central air conditioner tries to come on but won't. I hear it trying to come on. The unit is attached to a "Beat The Peak" system. Could that be causing the unit to not come on?

Heat runs with ac and even auto kicks on emg heat [ 1 Answers ]

(Coleman Evcon) Some how the hot and cold on the inside thermostat switched.how is that possible?and how do I fix it?

Blower kicks on and off [ 1 Answers ]

Will I read a lot of questions very much like mine, but I'm a person who knows nothing about the furnace. All I know is that it's COLD here. We changed the filter a couple days ago and we started hearing the furnace was kicking on and off. So we went down stairs to check it out. What we could see...

Weed eater ate my wiring to my central air compressor. [ 3 Answers ]

Need some help. I was weed eating around my outside coils and compressor when my weed eater cut the wire that runs from the 24 volt transformer inside. I connected the wiring back and now my air won’t come on. I have a Trane XE 60 furnace. I tried connecting “R” “Y” to see if the compressor would...


View more questions Search