    Central Air Blower not working.
    The blower on my central air unit is not working. It starts to hum and if I spin the blades (which spin freely) manually it turns on for a few minutes but then shuts off. I turned the thermostat to ON and cool. Not sure the model number all I know is it says Sears All Conditioner on the side of unit. Any help would be greatly appreciated.
    siberianair's Avatar
    siberianair Posts: 360, Reputation: -4
    Full Member
     
    #2

    Jun 23, 2009, 12:16 PM

    Sounds to me like one of the widnings has gone bad or your capacitor needs replaced.
    Spini3235's Avatar
    Spini3235 Posts: 4, Reputation: 1
    New Member
     
    #3

    Jun 23, 2009, 12:24 PM
    How would I know if it was one or the other??
    siberianair's Avatar
    siberianair Posts: 360, Reputation: -4
    Full Member
     
    #4

    Jun 23, 2009, 12:31 PM

    If you have a multimeter that can read microfared you can check the capacitor. If it is weak it will need replaced.

    You can try changing the fan speed and see if another winding works. If you can read a wire diagram it will show you what speed is high medium and low and where to place them on board to change speeds.

    If you could find the model and seriel number it would help. Now adays sears units arer made by carrier corp and might be able to find a wireing diagram.

    How old is the unit by the way?
    Spini3235's Avatar
    Spini3235 Posts: 4, Reputation: 1
    New Member
     
    #5

    Jun 23, 2009, 01:14 PM
    The Wiring Diagram is on the door of the unit, so I was able to try the other speeds and I was still having the same problem. My multimeter does not measure microfarad So I am not sure about the capacitor. I can not find anything on the model or serial number on the whole unit all it says is Sears All Conditioner...
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #6

    Jun 23, 2009, 02:37 PM

    Usually if the motor start by hand and stays running, it's a bad cap. However in your case the motor starts only for a short period. I would still get the cap checked, or even replace it(they are cheap), but I'm betting your motor is in need of replacement.
    Spini3235's Avatar
    Spini3235 Posts: 4, Reputation: 1
    New Member
     
    #7

    Jun 24, 2009, 02:52 PM

    Thanks everybody for your help I changed the capacitor and the blower is running great again. Thanks again!
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #8

    Jun 24, 2009, 02:58 PM

    Glad that fixed it.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Central Air blower not working [ 17 Answers ]

My central air conditioning blower is not working. Fan on outside unit works but inside fan does not. When I manually turn the fan on at the thermostat it still does not work. What do I need to check?

Blower not working and blower running all the time [ 2 Answers ]

I have a Lennox electric furnace that's about 10 years old or so, the elements come on but no blower. There is a summer fan switch that will make the blower run when switched on, but it will not come on with a call for heat. Also at my work, there is a york gas pack that is probably 15 years old....

Heat and Air not working on Attic unit, but blower working. [ 1 Answers ]

The blower is working fine on our Heating and Air Conditioning unit but neither the Air or Heat will work. The emergency Heat works fine though. The unit is a Carrier with the words American Standard written on the outside fan unit. What should I look for before calling a tech or what would this be...

Central AC with gas furnace blower not working [ 3 Answers ]

The house was getting hot so I checked the thermostat and discovered there was no air coming out of the vents. The outside unit comes on but no noise from up in the attic. I had no problems earlier in the day. The fan doesn't come on in the auto or on position.:confused:

Central indoor fan blower not working [ 11 Answers ]

Hi, My indoor blower quit working, first it made weird sounds during start few times and then quit. I have a Rheem Criterion furnace from 1992. The air handler and evaporator was replaced few years ago and other maintenance done. The run capacitor (Old one was a cylindrical 15MFD 370VAC...


View more questions Search