    Carrier overheating, Code 33
    I'm having problems with high limit switch tripping every 5 to 10 minutes, code 33 on Carrier 58sta070 13112 manufactured 2008. Flue is clean, blower has new capacitor and runs fine on fan, new thermostat, no blocked registers and good airflow, only shuts down when filter is put in even with the thinnest one I can find. 16X20X1, but manual says 16X25X1 is needed. Is it probable that this is causing my problem?
    smoothy's Avatar
    smoothy Posts: 25,492, Reputation: 2853
    Uber Member
     
    #2

    Jan 27, 2018, 10:39 AM
    Quote Originally Posted by CrowdSpectator View Post
    I'm having problems with high limit switch tripping every 5 to 10 minutes, code 33 on Carrier 58sta070 13112 manufactured 2008. Flue is clean, blower has new capacitor and runs fine on fan, new thermostat, no blocked registers and good airflow, only shuts down when filter is put in even with the thinnest one I can find. 16X20X1, but manual says 16X25X1 is needed. Is it probable that this is causing my problem?
    Both are both just as thick, 1"... ones a lot smaller around than the other. Length x Width x thickness (height in this case) , but air should be flowing AROUND it in this case.. at least partially depending on how much overlap you have.
    CrowdSpectator's Avatar
    CrowdSpectator Posts: 4, Reputation: 1
    New Member
     
    #3

    Jan 27, 2018, 10:43 AM
    Thanks for the quick reply, but I failed to mention that the side return between the vertical stack and the side of the furnace is only big enough for a 16x20 to fit.
    talaniman's Avatar
    talaniman Posts: 54,327, Reputation: 10855
    Expert
     
    #4

    Jan 27, 2018, 11:28 AM
    When you checked your flue did you also check your furnace evaporator coils?

    https://www.youtube.com/watch?v=DA_F_-0F5zc
    CrowdSpectator's Avatar
    CrowdSpectator Posts: 4, Reputation: 1
    New Member
     
    #5

    Jan 27, 2018, 11:31 AM
    Yes sir, I did and had it cleaned. Also the blower motor and wheel are cleaned, flame sensor is new. No cracks in exchanger.
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #6

    Jan 27, 2018, 12:03 PM
    If you are you getting good airflow through the registers, the flue is clean and no flame spill out, I'd replace the limit switch. Does yours auto reset or do you push a button? They are typically less than $10. If it still continues, I would say blocked airflow in the system.
    talaniman's Avatar
    talaniman Posts: 54,327, Reputation: 10855
    Expert
     
    #7

    Jan 27, 2018, 01:56 PM
    only shuts down when filter is put in even with the thinnest one I can find. 16X20X1, but manual says 16X25X1 is needed. Is it probable that this is causing my problem?
    If your furnace runs fine without the filter, then you are not getting enough air flow to move the heat build up, which triggers the code 33. It may be the type of filter, and you need one that allows more air to be sucked in, or you may have to do as this smart fellow did,

    https://www.youtube.com/watch?v=Bb2_cgy5Ufo (I find it useful to scroll down and read the comments under the video)

    It may be some changes have been made, unless somebody screwed up, if your model calls for a larger filter than you can fit. Something to check, and verify. At this point, though, you must also verify your induction motor is moving air properly, even after you changed the capacitor and cleaned the blades (squirrel cage thingy). That's done with a multi meter.

    I verified the correct size filter for your furnace, and it does not match what you have...WTF?!

    ALSO

    https://www.repairclinic.com/RepairH...-58STA07015112

    CAUSE 12
    CrowdSpectator's Avatar
    CrowdSpectator Posts: 4, Reputation: 1
    New Member
     
    #8

    Jan 27, 2018, 03:57 PM
    Thank you all for your time and input. Besides replacing the high limit switch, I fear the rest of this is out of my limits and I'll need to call in a technician. I appreciate your input
    Fr_Chuck's Avatar
    Fr_Chuck Posts: 81,301, Reputation: 7692
    Expert
     
    #9

    Jan 27, 2018, 05:45 PM
    http://dms.hvacpartners.com/docs/100...c/02/58-3T.pdf

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Carrier Furnace Models 58pav090-14 I have a Carrier 58PAV090. The LED error code is f [ 1 Answers ]

I have a Carrier 58PAV090-14. The LED error code is flahing 12. The draft fan starts. Ignitor glows. Flame starts. Heats up. Blower starts and runs 5 seconds then all stops. I swapped the pressure switch and flame sensor with my other, identical unit that is working. No luck. Help?

Carrier code 33 [ 0 Answers ]

I replaced circuit board blower motor capacitor. Now the blower stay on and give code 33. And the furnace will not ignite. A new filter is installed.

Carrier furnace with a red flash code of 2 short and 1 long code [ 2 Answers ]

I have a Carrier and the furnace and the heat will not come on. The fan does come on but the burners will not ignite. I get a red flash code of 2 short and one short. I have the same thermostat upstairs and I switched them and the same result. The upstairs works fine with both thermostats. I have a...

My carrier furnace LED light is flashing a code. How do I tell what code it is? [ 1 Answers ]

The error code is flashing and I know certain lengths, long and short indicate a code but how do I tell which one it is?

Carrier code 45 [ 1 Answers ]

Carrier furnace flashing a code 45 says replace control. Which control? Control board, thermostat or what?


View more questions Search