    errmpc4940's Avatar
    errmpc4940 Posts: 3, Reputation: 1
    New Member
     
    #1

    Nov 5, 2009, 05:33 PM
    Carrier furnace blower will not shut off
    I have a 13 yr old Carrier Weather Maker 8000 gas furnace. It heats fine. However, earlier this week, after reaching the set temperature, rather than shutting off the blower kept running, eventually blowing cool air. What's crazier, even after switching the thermostat (a programmable type) to Off the blower keeps running.

    I've checked the circuit breaker, even flipping it off and on.
    I changed the batteries in the thermostat.
    I followed the directions and powered down the furnace, including shutting off the gas, waited the allotted time, then powered it back up.

    The blower keeps running. The only way to shut it down is to flip the on/off switch located on the furnace itself, which I do before going to bed.

    Any ideas?

    Thanks.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Nov 5, 2009, 05:44 PM
    Try this: increase thermostat setpoint above room temperature to initiate heating cycle, and listen for heating cycle to begin. From that point, does the blower stop after about 30-40 seconds, then re-start about 30-40 seconds later? Or does it run continuously throughout this test? Post back with results.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #3

    Nov 5, 2009, 07:32 PM
    I know this sounds crazy but I have to ask is the fan switch in the on position on the thermostat? If not but the system is heating you have a stuck relay on the control board. No danger but it will need to be replaced to get the blower to cycle.( I run my blower 24/7 it never shuts off)
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Nov 5, 2009, 08:01 PM
    Quote Originally Posted by T-Top View Post
    I know this sounds crazy but I have to ask is the fan switch in the on position on the thermostat? If not but the system is heating you have a stuck relay on the control board. No danger but it will need to be replaced to get the blower to cycle.( I run my blower 24/7 it never shuts off)
    Not so crazy at all. If the blower doesn't pause during the test, either the relay contacts have fused or the timing logic of the board has failed. If the board is good, blower will pause regardless of fan switch setting.
    errmpc4940's Avatar
    errmpc4940 Posts: 3, Reputation: 1
    New Member
     
    #5

    Nov 6, 2009, 08:49 AM
    Quote Originally Posted by KC13 View Post
    Try this: increase thermostat setpoint above room temperature to initiate heating cycle, and listen for heating cycle to begin. From that point, does the blower stop after about 30-40 seconds, then re-start about 30-40 seconds later? Or does it run continuously throughout this test? Post back with results.

    The blower runs continuously.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #6

    Nov 6, 2009, 09:48 AM
    Faulty circuit board. On the upside, the system will still heat if a new board isn't in the budget right now.
    errmpc4940's Avatar
    errmpc4940 Posts: 3, Reputation: 1
    New Member
     
    #7

    Nov 6, 2009, 10:04 AM
    Quote Originally Posted by KC13 View Post
    Faulty circuit board. On the upside, the system will still heat if a new board isn't in the budget right now.


    I appreciate your help. Thanks.
    SherrynDavids's Avatar
    SherrynDavids Posts: 1, Reputation: 1
    New Member
     
    #8

    May 23, 2010, 11:55 PM
    Is this circuit board in the thermostat on the wall??

    I had this same problem a ouple of years ago and the service call cost me more than the part. I replaced the thermostat and it worked great, but today I'm back to the blower not shutting off again.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Carrier gas furnace fan won't shut off [ 23 Answers ]

We have a 21 yr. old Carrier gas furnace and I just changed the air filters. When I put the cover back on, even though the thermostat was turned to off, the fan started. I even disconnected the thermostat, but the fan kept going. It runs 24/7. When I finally turned the thermostat to "auto",...

Carrier AC blower does not shut off [ 13 Answers ]

I have a new Carrier package unit which we bought 5 months ago. All of a sudden the blower does not shut off and constantly runs. It occasionally cyles off and on. The compressor does not kick in and it shouldn't because it is set to turn on at 77 degrees and the house is an average 70 degrees. It...

Carrier Air Handler - Blower Won't Shut Off [ 3 Answers ]

I have a Carrier heat pump package unit with a Carrier air handler, both from late 70's/early 80's (Model number illegible on sticker). When the weather was cold a couple of months ago, the blower would run constantly, making the house unbearably hot. Turning down, turning off, or disconnecting the...

Carrier furnace blower no shut off except power [ 3 Answers ]

I have a carrier furnace. The blower is not shutting off, even when the thermostat is set to off. Could it be the thermostat unit? The relay? The circuit board on the carrier? A fan switch somewhere? Where is the best place to start diagnosing this problem? And in what order should it be done? ...

Carrier furnace blower fan doesn't shut off [ 1 Answers ]

Hi my carrier furnace the blower fan that circulates air through the duct work doesn't stop running Thanks jim


View more questions Search