    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #1

    Nov 20, 2008, 10:47 PM
    Carrier AC blower does not shut off
    I have a new Carrier package unit which we bought 5 months ago. All of a sudden the blower does not shut off and constantly runs. It occasionally cyles off and on. The compressor does not kick in and it shouldn't because it is set to turn on at 77 degrees and the house is an average 70 degrees. It began happening on what we Floridians call a cold night, 60 degrees. It is connected to a Riteaid electronic programmable thermostat we bought at Home Depot. It does not have a heater. I cannot find anything in the thermostat that could be causing the problem. What in the world could be causing this blower not to shut off? Blown fuse in the AC? The only way I got it to turn off is by cutting the power to the unit. Any help will be greatly appreciated.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 20, 2008, 11:04 PM
    If the unit is new it is under warranty. If you mess with the unit it can cause the warranty to be canceled. Why take the risk. Call the company that you bought it from. Most dealer warrentys parts and labor is one year form date of purchase.
    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #3

    Nov 21, 2008, 05:23 PM
    Quote Originally Posted by hvac1000 View Post
    If the unit is new it is under warrenty. If you mess with the unit it can cause the warrenty to be canceled. Why take the risk. Call the company that you bought it from. Most dealer warrentys parts and labor is one year form date of purchase.
    The problem is that the A\C was installed by myself and a buddy of mine from work, yes I know mistake number 1. Buddy of mine got the A\C wholesale through his dad's company. Company he bought it from won't honor anything if I don't know what is wrong with it.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Nov 21, 2008, 06:46 PM
    Blower relay could be the problem.

    It could also be the thermostat telling the blower to come on for some reason. Test this by disconnecting the G wire from the thermostat and see if the blower still runs sometimes
    BTTAndy's Avatar
    BTTAndy Posts: 1, Reputation: 1
    New Member
     
    #5

    Nov 21, 2008, 07:53 PM

    I have an older carrier unit in Michigan. The blower will not shut off and continues to blow when the flame is off cycle. The heat is fine but I am worried that this is nit efficient and could damage the motor. Is this a fuse? Do I need a new ignition module?

    Andy
    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #6

    Nov 26, 2008, 07:53 PM
    Disconnected the G wire to see if the thermostat was making the blower turn on for some reason and after disconnecting the G wire, the blower continued to run. I even reset the thermostat by pressing a small reset button in the Ritetemp thermostat and nothing, blower still runs continuously. Defective thermostat?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #7

    Nov 27, 2008, 12:12 AM
    If you disconnected the G wire from the tstat and the blower still runs it is not the tstat. It has to be a stuck relay OR something is wired wrong like the thermostat wires are shorted causing the problem.
    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #8

    Nov 27, 2008, 09:15 AM
    I will check the wiring and the blower relay. It ran fine for months and this started happening when the outside temperature dropped. Is it safe to assume that it could be a bad relay? I'll check both and let you know the outcome. Thanks for your help.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #9

    Nov 27, 2008, 09:31 AM
    It could be a bad relay but usually when they stick or the internal parts burn together they never turn off after that happens. You said it would sometimes turn off so that complicates the situation. Does the thermostat have a recycle schedule you can set just to circulate the air at different periods? Some thermostats do offer that as a option in the setup menu.
    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #10

    Nov 27, 2008, 03:53 PM
    Checked the wiring on the tstat as per the manual and it all seems to be correct. I only have three wires going to the tstat, Y=yellow, RH=red, G=green so it seems to be a bad relay. Would you have any idea where this relay would be located on a Carrier package unit? I just turned it back on and I'm going to see if it turns off which I have a feeling it will not, I'll let you know. Given the fact that it started happening all of a sudden after a few months would point to a relay and not wiring, wouldn't you agree?

    Well, off to eat Thanksgiving with the family, wish you and your family a happy thanksgiving and thanks again for the help.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #11

    Nov 27, 2008, 04:30 PM
    If you disconnect the green wire on the outside unit and the blower still runs then the relay has to be bad in my opinion since this is a package unit and everything is outside except the thermostat. Now if you disconnect the green wire in the outside unit and the blower shuts off then you know they thermostat wire or thermostat is causing the problem.
    Does this unit have heat?
    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #12

    Nov 28, 2008, 01:37 PM
    I have left the AC on AUTO fan and COOL for 24 hours and the blower cyles on and off randomly without engaging the compressor. I am going to try what you said and let you know.
    flopez1974's Avatar
    flopez1974 Posts: 8, Reputation: 1
    New Member
     
    #13

    Nov 29, 2008, 02:21 PM
    Replaced the tstat and it seemed to have fixed it. I think it was a defective thermostat. I replaced the stat with a plain jane non-programmable one. Thanks for all your help.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #14

    Nov 29, 2008, 02:24 PM
    Good deal. Glad to see it is working. Some thermostats of the program type will allow a setting for the blower to run every 15 to 60 minutes depends upon how programed.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Carrier Weathermaker SX Intermittent shut down [ 2 Answers ]

I have a early 1990's Carrier Weathermaker SX furnace, model 58SXA100, with a hard to diagnose problem. Every so often it will fail to start when the tstats call for heat. I have a 3 zone set-up, all of the tstats are new, same model and have been checked for the proper voltage. The circuit...

Carrier gas furnace fan won't shut off [ 23 Answers ]

We have a 21 yr. old Carrier gas furnace and I just changed the air filters. When I put the cover back on, even though the thermostat was turned to off, the fan started. I even disconnected the thermostat, but the fan kept going. It runs 24/7. When I finally turned the thermostat to "auto",...

Carrier Air Handler - Blower Won't Shut Off [ 3 Answers ]

I have a Carrier heat pump package unit with a Carrier air handler, both from late 70's/early 80's (Model number illegible on sticker). When the weather was cold a couple of months ago, the blower would run constantly, making the house unbearably hot. Turning down, turning off, or disconnecting the...

Carrier furnace blower no shut off except power [ 3 Answers ]

I have a carrier furnace. The blower is not shutting off, even when the thermostat is set to off. Could it be the thermostat unit? The relay? The circuit board on the carrier? A fan switch somewhere? Where is the best place to start diagnosing this problem? And in what order should it be done? ...

Carrier furnace blower fan doesn't shut off [ 1 Answers ]

Hi my carrier furnace the blower fan that circulates air through the duct work doesn't stop running Thanks jim


View more questions Search