    Carrier 58SS blows 2amp inline fuse on 24 volt line to limit switch.
    My carrier SS furnace blows the inline @amp fuse to the limit switch and then blows cold air continuosly . Is my low voltage supply faulty or do I have a wire grounding out somewhere.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Nov 6, 2009, 10:05 AM
    When does the fuse blow? Immediately after turning on power to the unit, or after some operation is initiated? Try disconnecting all thermostat wires from the circuit board to determine if the short is within the furnace or elsewhere.
    rumscheid's Avatar
    rumscheid Posts: 3, Reputation: 1
    New Member
     
    #3

    Nov 6, 2009, 11:06 AM
    The fuse blew after several hours of operation. It was in the middle of the night. I replaced the fuse and now I have no power to the thermostat.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Nov 6, 2009, 04:39 PM
    Is it a digital thermostat, and the display isn't coming up? If you have a voltmeter, did you check for 24v from the "R" circuit wire to any of the other wires?
    rumscheid's Avatar
    rumscheid Posts: 3, Reputation: 1
    New Member
     
    #5

    Nov 6, 2009, 09:37 PM
    No it is a regular not digital thermostat but I changed it anyway and still have the problem of blowing the fuse. I have now tested all the wiring and the thermostat and am wondering about the circuit board with the 2 relays built in. Could a relay with bad points throw enough of a amperage fluctuation to blow the fuse. The circuit is back working with a new fuse so tonight will see if it continues to be a problem with the new thermostat.
    Dangerman's Avatar
    Dangerman Posts: 1, Reputation: 1
    New Member
     
    #6

    Mar 10, 2010, 03:35 PM
    The Carrier 58SS furnace does not have an inline fuse on the limit circuit. It does have what is called a fuseable link located directly on one of the two main limit terminals. Although it looks like an electrical fuse it is "tripped" by heat. The fuseable link is a safety device used to monitor the flames and venting of the furnace and should never be replaced by a homeowner more than once. Call a qualified heating company to check out the system.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Carrier furnace blows 3 amp fuse after burner and blower fan have been on For a while [ 0 Answers ]

Carrier furnace with 4 LED control board 3 amp fuse opens after burner and circulation fan has been on for awhile 26Vac pulls down to 8 volts ac Replaced with 5 amp fuse and it does not open and furnace operation seams normal. Valve control is a White Rodgers 36E What should the resistance of...

Water pressure switch blows fuse [ 3 Answers ]

Our submersible pump stopped working so I replaced the pressure switch. I was very careful to wire the new switch the same as the old one, however the new switch blew a fuse when I turned the power on. I then thought I would try cleaning the points on the old switch with emery cloth and try it...

Carrier 58ss cycling [ 83 Answers ]

I had about the same problem last heating season. One repairman said it needed a new control board and then online I read about the pilot ignitor. I replaced stark electrode and pilot burner and it seemed to fix it. The it started again so since I bought the control board online previous, I put...

ICM271 Carrier Replacement board Fuse blows [ 4 Answers ]

My Furnace recently stopped working and the Furnace Fan stayed on constantly. I replaced the original Fan Control circuit board (HH84AA011) with a ICM271 drop in replacement board. Still nothing came on, not even the constant fan. I check the 120V-24V transformer and found no 24V output so I...

Limit switch pops out, furnace blows cold air, also slow water leak [ 2 Answers ]

I have a series 100 carrier gas furnace (15 yrs old) I reset the limit switch, turn the power back on at the furnace. It starts up fine and the burners come on for about 15 minutes or so then the limit switch pops out and the fan keeps blowing out cold air. There is a slow dripping of water on...


View more questions Search