    Carrier 58DLA LED rapid flashing, air blows no heat
    My issue is with a Carrier Weathermaster 8000 furnace, 58DLA. When I turn on the heat, the air blows but no heat, and after a couple of minutes it shuts off.
    A couple of weeks ago the gas line was shut off for a couple of days, and I never tested the heat after that, but the boiler is on the same gas line under the furnace, so I know gas is going through.
    The status light blinks constantly, there is no code sequence. This indicates 115VAC polarity reversal, but this is impossible, since no work was done on wiring. Or a twinning issue, but I have only one.
    The air conditioning works fine, 120VAC tested fine coming out of the circuit board. I even swapped the 120VAC coming into the furnace, and it still has continuous rapid flashing no matter what.
    I've read on similar problems that indicate a grounding issue on different brands of furnaces, but not sure about that out of the blue, it's been working like this for 8 years without issues like this.
    Any help would be appreciated.
    dken7's Avatar
    dken7 Posts: 9, Reputation: 1
    New Member
     
    #2

    Oct 18, 2010, 06:48 PM
    Check the gas valve and see if there is constan power on it. The coil on the valve could be stuck.
    kerty's Avatar
    kerty Posts: 10, Reputation: 1
    New Member
     
    #3

    Oct 19, 2010, 06:14 AM
    Thanks, it ended up being the board
    mikebaum's Avatar
    mikebaum Posts: 2, Reputation: 3
    New Member
     
    #4

    Nov 28, 2011, 10:35 AM
    I traced the board I have to two jfets j211 and j176. I looked at the specs (I'm an EE) and the J211 is an RF jfet. I replaced it with the switching type j112 (and the j176 with a new one). Board works fine. I wonder if they loaded the boards mistaking the j112 for a j211? Both are n channel jfets. Who knows?
    kerty's Avatar
    kerty Posts: 10, Reputation: 1
    New Member
     
    #5

    Nov 28, 2011, 10:57 AM
    Thanks mikebaum, I still have the old board, so I will definitely do what you did to fix it! Won't hurt to have a backup board. Good q's though. Do you have part numbers/descriptions for those 3 jfets? And where is the best place to get them?
    mikebaum's Avatar
    mikebaum Posts: 2, Reputation: 3
    New Member
     
    #6

    Dec 6, 2011, 02:36 AM
    My board is in the attic furnace now so by memory: If your board is the same as mine then there is a large chip made by microchip near the middle. Beside the chip is two parts (look up TO-92 case) labeled Q on the board and then a number. On those parts one is a J211 (with other numbers after) in small letters on the flat side of the case. The other is a J176 (with more numbers). I am just guessing here but it seems to me that somewhere there was a mix up. I am hoping this will help others as well. It looks like these parts are part of conditioning the signal for AC sense. In the configuration they are using these JFETs it would be better to use a switch type J112 instead of a radio frequency type J211. The J112 is also a close match for the complement of the J176. The J112 is much more robust than the J211 and that is probably why so many people have had this problem. These parts can be ordered from Digi-Key or Mouser.
    kerty's Avatar
    kerty Posts: 10, Reputation: 1
    New Member
     
    #7

    Dec 6, 2011, 09:53 AM
    Thanks for the details, I'll try that out!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman Air furnace - Diagnostic LED is Flashing One Time [ 0 Answers ]

The owner manual says this flashing means the furnace is in a lockout mode. I tried to shut down the power to the furnace for about 5 minutes and started again as suggested. But the blower fan comes on and runs for about 30 seconds and nothing happens. This continues for another couple of times and...

Goodman Air furnace - Diagnostic LED is Flashing One Time [ 1 Answers ]

The owner manual says this flashing means the furnace is in a lockout mode. I tried to shut down the power to the furnace for about 5 minutes and started again as suggested. But the blower fan comes on and runs for about 30 seconds and nothing happens. This continues for another couple of times...

Carrier infinity weathermaker flashing yellow led. No heat [ 1 Answers ]

Woke up this morning.. my thermostat(non-carrier) showed no digits... I asumed it was broken... replaced it with a no digital type(slider)... got no heat but cool air coming out of vents... Went downstairs to inspect furnace... got a yellow blinking led... one short... three long... Any ideas?

Carrier Heater won't shut off! Blows only cool air. Heat won't work! [ 1 Answers ]

Does anyone know what I can do? My carrier heater is only 2 years old. As of yesterday the heater unit wouldn't shut off and when I turn the heat up it just keeps blowing cool air. I heard I can trip a breaker switch. Is that the electrical switch in the garage or on the heater itself? Please let...

CARRIER 58RAV Furnace Blows Cold Air-No Heat [ 1 Answers ]

I have a Carrier Model # 58RAV50-13112 Gas Furnace (fueled by propane) that isn’t working properly. It’s a holiday weekend and I’m without heat, so any help would be greatly appreciated. The furnace was operating properly throughout last winter. However, now it‘s not working. The fan runs but...


View more questions Search