    Can R410 air handler work properly with a R22 condenser in a heat pump
    I have a split system heat pump (Carrier). Due to freon leakage, contractor through home warranty replaced indoor fan coil with a new one (Payne) that works with R410. I was told that they installed an expansion valve too. The outdoor unit is still R 22. He charged with R22 at the time of installation. The air I'm getting now is not cool. Is this because of the incompatibility of the indoor and outdoor unit? What options do I have? Can I simply replace the condenser to a R410 system, or I have to replace the indoor air handler as well?
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Jun 17, 2013, 12:47 PM
    Incompatible systems, valving and piping different. 410 compressor has much more head pressure. Have the condenser changed and recharge with 410. Since the A-Coil fits, no need to change air handler.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Are air handlers compatible with R22 and R410? [ 6 Answers ]

The drip pan in my 16-year old York A/C is rusty and needs to be replaced at a cost of $850. The original installer says it isn't worth it and recommends replacing the air handler at a cost of $3800. He said we can wait until the condenser fails before replacing it. A second company suggested...

Heat pump air handler [ 1 Answers ]

Weather king air handler & heat pump can not fing out which wires to use for a/c out of handler red,white&blue,white&black,brown,green&black which two wire for a/c

Heat pump condenser replace - R22 vs R410 [ 9 Answers ]

I have 25 yr old SEER 10 GE heat pump. Heat exchanger is in excellent condition. If I go to R410 I need to replace lines and both units. If I stay R22 I can do only condenser. If I go to SEER 16 do I get any benefit or do I just do the SEER 13. As I get it, either way I only need to replace...

I have an existing R22 w/ an R410 AC Heat Pump [ 5 Answers ]

I have an existing R22 ac heat pump, I am replacing it with a R410 unit, how do I get the air to run now?


View more questions Search