    aterbrys0528 Posts: 2, Reputation: 1
    New Member
     
    #1

    May 25, 2007, 10:03 PM
    A/C keeps blowing fuse
    I had an earlier post about neither the furnace or a/c working... well the problem was a blown fuse, and I have no idea why I didn't find it earlier. Anyway, I replaced the fuse and the furnace heat now works, but when I go to the a/c, the fuse blows every time. My furnace takes a little 5 amp buss fuse. Any clue as to why this is happening? Would it be safe to try to use another fuse with a higher amp rating?
    ems348's Avatar
    ems348 Posts: 3, Reputation: 1
    New Member
     
    #2

    May 25, 2007, 11:33 PM
    Quote Originally Posted by aterbrys0528
    I had an earlier post about neither the furnace or a/c working...well the problem was a blown fuse, and I have no idea why I didn't find it earlier. Anyway, I replaced the fuse and the furnace heat now works, but when I go to the a/c, the fuse blows everytime. My furnace takes a little 5 amp buss fuse. Any clue as to why this is happening? Would it be safe to try to use another fuse with a higher amp rating?
    Changing the amp rating could cause overloading and overheating of the wiring. Not a good idea. I would check the amp draw of the air conditioner. You may need to put it on a different circuit, or take some other things off that circuit to try to stop the fuse from being overloaded. The best solution would be to have an electrician check it out. If not, or can't afford it, try contacting your local Fire Prevention Bureau, some of those FF can really help you out.
    JackT's Avatar
    JackT Posts: 260, Reputation: 19
    Full Member
     
    #3

    May 27, 2007, 06:01 AM
    You must be referring to the low voltage fuse and not the line voltage fuse. If the 5 amp fuse only blows when you switch it over to the cooling mode, you probably have a problem with the condensing unit. Check the small 24 volt wires going outside to the unit. If they appear to be in good condition you probably have a problem inside the condensing unit. Depending on the make and model, it could be the coil on the contactor, time delay relay, or the circuit board itself or the reversing valve coil. (if it's a heat pump)
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #4

    May 27, 2007, 09:09 AM
    Which fuse does it blow when you turn on the AC? The low voltage fuse or the high voltage fuse?
    Hokiez's Avatar
    Hokiez Posts: 4, Reputation: 1
    New Member
     
    #5

    May 28, 2007, 05:28 PM
    Quote Originally Posted by JackT
    You must be referring to the low voltage fuse and not the line voltage fuse (I'm assuming low voltage as when it blows, I have no 24V power to the thermostat). If the 5 amp fuse only blows when you switch it over to the cooling mode, you probably have a problem with the condensing unit. Check the small 24 volt wires going outside to the unit. If they appear to be in good condition you probably have a problem inside the condensing unit. Depending on the make and model, it could be the coil on the contactor, time delay relay, or the circuit board itself or the reversing valve coil. (if its a heat pump)
    I've got exactly the same problem though mine is only a 3 amp fuse. It's the one inside the unit. I know the compressor can turn as if I take the cover off and manually activate the plunger switch, it will turn on. The same compressor has had a problem where I've had to clean this same switch a bunch (10-15) times to get the unit to activate properly (it's 4 years old). Could this constant draw of power trying to turn on without actually turning on have fried something in the outside? Normally I can hear it buzzing with electricity, but now it doesn't even do this. I hear the thermostat click, then at most 15 seconds of blower activity, then dead, blown fuse.

    Thanks in advance for the help!
    JackT's Avatar
    JackT Posts: 260, Reputation: 19
    Full Member
     
    #6

    May 28, 2007, 06:46 PM
    You have something in your control circuit that's blowing the fuse. Check the small 24 volt wire that goes out to your outside unit for any shorts. If that appears to be in good condition, you most likely have a problem with the coil on the contactor, the time delay relay, or the control circuit board being bad. If you have a spare fuse, you can pull both wires off your contactor and turn on the ac. If the fuse still blows it's not the contactor and you'll need to look at some of the other items. If the fuse doesn't blow, change the contactor.
    Hokiez's Avatar
    Hokiez Posts: 4, Reputation: 1
    New Member
     
    #7

    May 28, 2007, 07:04 PM
    Thanks JackT for the quick response! That's a great suggestion. I'll try that as soon as I get home from work tomorrow and that makes a ton of sense (the contactor). In my marvelous electrical jargon I've referred to the contactor as the plunger switch which has been sticking for the past year and a half or so. Perhaps all that current draw finally killed it? My solution had been to clean it with electrical cleaner and then bang the side of the unit and it would then draw in but you could hear the buzz of the switch trying to draw in. I've checked all the wiring and don't see anything that looks ugly in there. Would it be sufficient to simply pull the electrical connection from the box next to the compressor or do I need to go into the compressor and pull the actual wires off the contactor?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #8

    May 28, 2007, 08:06 PM
    JackT has been posting good advice to this thread. If you have an intermediate connection outside, pulling the wires off there, would isolate the problem as being before or after it. Go for the easiest check first. If the fuse doesn't blow, then go into the contactor itself.
    JackT's Avatar
    JackT Posts: 260, Reputation: 19
    Full Member
     
    #9

    May 29, 2007, 02:50 AM
    I'd pull both of the wires off the contactor and then try it. Make sure you pull off both of them off just in case the coil is grounded out. Good Luck
    Hokiez's Avatar
    Hokiez Posts: 4, Reputation: 1
    New Member
     
    #10

    May 29, 2007, 05:49 AM
    You guys are the best! I pulled the 24V from the contactor, replaced the fuse, set to cold and viola, no blown fuse. Now to go get that contactor, it's supposed to be 92 today! Fortunately my upstairs unit is working, though it was a block of ice yesterday (don't let your wife put your cat box under the intake).
    Hokiez's Avatar
    Hokiez Posts: 4, Reputation: 1
    New Member
     
    #11

    May 29, 2007, 12:20 PM
    Success! I couldn't find the identical contactor in-stock so I found a square D equivalent of the GE I took out @ Grainger and viola, the compressor fired right up.
    JackT's Avatar
    JackT Posts: 260, Reputation: 19
    Full Member
     
    #12

    May 29, 2007, 01:04 PM
    aterbrys0528, Don't use a bigger fuse. If the fuse blows when the ac is turned on you probably have the same problem as Hokiez had above. You shouldn't blow a 5 amp control fuse unless you have a short in the control wires feeding your outside condensing unit or you have a bad control. I would suggest you follow the same steps that Hokiez did, unhook the wires outside or pull both wires off the contactor and see if the fuse still blows.

    Glad we could help you Hokiez,

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

92 Honda Accord, A/C Fuse keeps on Blowing out. [ 9 Answers ]

I have a 92 honda Accord EX. The A/C fuse (7.5A) (under the steering wheel) keeps on blowing out. Every time I replace it, it cools the car for 5 minutes and the A/C fuse is blown out again. I am not sure where to start diagnosing the problem. Any suggestions would be highly appreciated. One of...

Kenmore dryer blowing fuse. [ 1 Answers ]

Hi all, My Kenmore Heavy Duty dryer started causing trouble a while back when it started to leave grease marks on my clothes, and eventually it got to the point that it was chewing the occasional hole in some things as well. My husband and I took it apart to discover that the center drum support...

Keep blowing fuse [ 1 Answers ]

1998 Dodge Ram, been sitting for about a week, went to turn on windshield wipers and they didn't work. Check the fuse and it was blown. Changed fuse and as soon as I put it in the fuse blows. Did this several times and no luck. ANY IDEAS! THANKS,

94 honda civic keeps blowing taillight fuse [ 1 Answers ]

94 honda civic keeps blowing taillight/parking light fuse. Replaced switch didn't help. Unplugged all parking lights, turned on parking lights and the fuse blows. I believe it is a short but can't find it with a multimeter. Is there anything else to check?

Fuse in furnace blowing [ 4 Answers ]

My buddy has a payne heat pump system with a payne air handler and every time the heat is turned on at the termostat the fuse blows in the air handler cabinet. The fuse will not blow if emergency heat is turned on or the a/c what is the problem here? I have been working in hvac for six years but...


View more questions Search