    leatherman's Avatar
    leatherman Posts: 5, Reputation: 1
    New Member
     
    #1

    Aug 13, 2013, 06:40 PM
    A/C condenser fan stops after a few minutes
    Replaced the condenser fan motor, and both capacitors. Unit will run for a few minutes and the fan stops, the compressor is noisy as well. After the last test run I saw what looks like a relay pop out a little after I turned off the power. Its on a black block where all the wires connect to. Is this the problem? And what is that box called so I can order a new one if possible.

    At first I thought I may have wired it wrong, but I don't think it would run at all if I did goof that up?

    This is an old central air unit, but I want to keep it running as long as possible.

    Thanks for any help.
    Johnson64's Avatar
    Johnson64 Posts: 6, Reputation: 2
    New Member
     
    #2

    Aug 13, 2013, 07:52 PM
    The black box will be either your contactor or relay. If you have had any power surges a storm recently that might be your problem. Best thing to do is to get it tested.
    leatherman's Avatar
    leatherman Posts: 5, Reputation: 1
    New Member
     
    #3

    Aug 13, 2013, 08:08 PM
    Thank you so much! Its one of the last things besides the compressor to replace now, well, that and the blower motor inside. Nickles and Dimes.

    Edit to add: if anyone has anything else I should be checking or replacing please do let me know, its August in Texas and we're getting desperate but not much money limits our possibilities.
    leatherman's Avatar
    leatherman Posts: 5, Reputation: 1
    New Member
     
    #4

    Aug 14, 2013, 09:45 AM
    Quote Originally Posted by leatherman View Post
    Thank you so much! Its one of the last things besides the compressor to replace now, well, that and the blower motor inside. Nickles and Dimes.

    Edit to add: if anyone has anything else I should be checking or replacing please do let me know, its August in Texas and we're getting desperate but not much money limits our possibilities.
    Did some more testing this morning, the relay works correctly, but shows some blackening around the contacts. With the power off to the condenser the inside unit turned on the relay closes nice and firm, when the inside is turned off it opens with authority.

    Note from yesterdays testings, the motor gets HOT before it stops after a few minutes. After some research I have a whole list of things to check. The two capacitors are new, but should probably be tested, that said is there a front and back on the two poles on these things? I've read about reversing the wires but I don't want to try that until I'm sure I am not going to blow it up.

    It seems that, from what I've researched, its down to capacitors or wiring, and maybe that switch. Wondering if I should take them all to the Grainger for testing. Lots of wires to keep track of though.
    leatherman's Avatar
    leatherman Posts: 5, Reputation: 1
    New Member
     
    #5

    Aug 14, 2013, 04:07 PM
    Well, I did replace the contacter, and the condenser fan motor still stops after a few minutes.

    I'm at a loss, over 200.00 and not any improvement.
    Johnson64's Avatar
    Johnson64 Posts: 6, Reputation: 2
    New Member
     
    #6

    Aug 14, 2013, 06:25 PM
    If there's a Grainger near you then sit in the parking lot and wait for a Heat & Air guy to show up and ask him... from my experience with them they will give you some advice
    Grady White's Avatar
    Grady White Posts: 1,417, Reputation: 59
    Ultra Member
     
    #7

    Aug 14, 2013, 06:30 PM
    You replaced the condenser fan motor & capacitor but are you sure the cap is the correct one for the motor? Just because it was the same as the old one means nothing. The cap has to be matched to the motor.
    leatherman's Avatar
    leatherman Posts: 5, Reputation: 1
    New Member
     
    #8

    Aug 14, 2013, 07:31 PM
    So far so good, I reversed the wires on the capacitor, brown/white and solid brown as per a suggestion and its humming along now.

    The guys at Grainger matched the capacitor and motor at the store thank goodness. I have honestly never been to a parts supplier, auto and such, that were as knowledgeable as these guys are. I am a very happy customer, and their tech support is second to none.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Ac condenser fan stops abruptly [ 1 Answers ]

Replace my ac condenser fan motor last year. It works fine now,but when it turns off, it stops abruptly and loudly. Is it going bad again?

Outside fan stops running after about 3 minutes.. [ 11 Answers ]

Today I washed off my outside A/C unit since I had recently bought the house and the p/o's weed eated and such constantly around it but never washed the thing off.. It had a lot of dirt and grim in the fins so I decided it would best if I took the fan and grill's off and washed the grills and fins...

Fan stops after a few minutes [ 2 Answers ]

Please someone help me. My central unit compressor sounds as if it is trying to kick on but doesn't start up completely when turned on. The fan turns, but not at full speed and after a few minutes, the fan stops and then the compressor makes a bad noise. Sounds to have a slight squealing sound...

Condenser Fan stops after an hour [ 1 Answers ]

To get the condenser fan working I have to use a stick something to get it started each time I turn the air on. Once started it will run for about an hour or so. What do you think the problem might be?

New Condenser Fan runs for 5 minutes [ 4 Answers ]

New Condenser Fan Motor runs 5 minutes then quits,however compressor continues to run ,I turned off the t-stat demand. Fan seems warm to the touch,will start up after 30 minutes or so please advice


View more questions Search