    A C Compressor not running
    I have a Carrier Model # 40AQ036330EH A/C, Heat pump unit installed in my home.
    I was working fine yesterday, but today the inside fan runs, but the outside unit is not running. I checked the main breakers in the garage and found one side tripped. I reset the breakers inside and outside with no change.
    I measured the power output at the outside contact with a multimeter, the reading shows no volts.
    Would this be a breaker problem or a transformer?

    Thanks for any help

    Tom:confused:
    Credendovidis's Avatar
    Credendovidis Posts: 1,593, Reputation: 66
    -
     
    #2

    Mar 27, 2008, 05:59 PM
    Quote Originally Posted by 3 thumbs
    I have a Carrier Model # 40AQ036330EH A/C, Heat pump unit installed in my home.
    I was working fine yesterday, but today the inside fan runs, but the outside unit is not running. I checked the main breakers in the garage and found one side tripped. I reset the breakers inside and outside with no change.
    I measured the power output at the outside contact with a multimeter, the reading shows no volts.
    Would this be a breaker problem or a transformer?

    Thanks for any help

    Tom:confused:
    Most probably a breaker problem.
    What is more connected to the same power circuit?
    Note that the switch "on" induction pulse of a compressor is high. Current can exceed 20+ Amps for 1 second, and that could trip a fuse. Specially if any other power circuit is connected to the same fuse.
    Success. Contact me if you can't solve the problem. May be with your findings there is more advice.
    ;)
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #3

    Mar 27, 2008, 06:33 PM
    Turn your thermostat off, then reset your breaker again(flip it all the way to off and then to on). If you have voltage then turn the thermostat back on. If you did not have voltage I would say a bad breaker. If it trips after you call for cooling you have problems with the out side unit---Bad run or start capacitor, burnt and shorted wire on the contactor,compressor or fan motor.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Goodman Heat Pump compressor keeps running [ 1 Answers ]

In Heat mode, compressor outside continues to run even when the blower inside is not running. If I switch the thermostat switch from Heat to off, the compressor stops but sometimes kicks back on, even with the thermostat switch still in the off position. At this point, I have to cut power via the...

Compressor quit running on my central AC [ 8 Answers ]

I have an older Rheem central AC unit at my house, I'm afraid I can't find the model number anywhere. The compressor quit running but the fan still runs. I've played around with the unit, the contactor is working and if I bypass the capacitor for the compressor I can get it to run for about a...

Air conditioner compressor not running. [ 1 Answers ]

My air conditioner fan runs outside but the compressor does not come on. Why

Blower will not come on but compressor is running [ 5 Answers ]

I am having a problem with my a/c unit. I have had the HVAC people hear 7x and they can't seem to find the problem. They changed the thermostat thinking that was the problem but it only worked for about 3 hours after they did that. They said they were going to call the tech people with the mfg...

AC compressor not running [ 10 Answers ]

My AC froze up and stopped cooling. I turned the ac off, and put the fan in run mode until the ice melted. When I turned the unit back on, the compressor did not come on. It is an Amana, just over 3 yrs old. Bruce


View more questions Search