Ask Experts Questions for FREE Help !
Ask
    OttoPilot's Avatar
    OttoPilot Posts: 3, Reputation: 1
    New Member
     
    #1

    Jul 14, 2008, 03:41 PM
    A/C 24v getting 120v when condenser kicks in
    I'm scratching my (sweaty) head with this one.

    Last fall I disconnected my A/C unit to accommodate an extension on my house. At the time it was disconnected, everything worked fine.

    I reconnected it in its new location. Ran 240V service and a new 18/2 control wire. I connected the control wire just as it was previously. When I turn on the unit from the thermostat everything starts fine but then when the condenser kicks in, the contactor sparks and the condenser stops working. I replace the contactor and nothing changed. I started troubleshooting with a volt meter and found that when the condenser kicks in I get a reading of 100+ volts on the 24V side. I can't find anything shorted out.

    Any idea on what might be causing this?

    Also, if I hold the contactor in manually the unit runs fine. I'm cooling my house now but there is no thermostat in the loop.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    Jul 14, 2008, 03:54 PM
    Follow control wiring closely, and especially check out if pulled tight on contactor lug.
    If it had 120 present at contactor coil, it will likely need to be replaced. Being a transformer, you may luck out with contactor being a transformer.
    You could have outside disconnect Off and turn inside unit on and to Cool. It should put 24 volts out to contactor coil. Verif it pulls contactor down, if not replace.
    Then turn on outside disconnect, if it now goes to 120 volts for some strange reason, you know it is from load side of disconnect to compressor and fan.
    OttoPilot's Avatar
    OttoPilot Posts: 3, Reputation: 1
    New Member
     
    #3

    Jul 16, 2008, 06:16 AM
    Quote Originally Posted by Stratmando
    Follow control wiring closely, and especially check out if pulled tight on contactor lug.
    If it had 120 present at contactor coil, it will likely need to be replaced. Being a transformer, you may luck out with contactor being a transformer.
    You could have outside disconnect Off and turn inside unit on and to Cool. It should put 24 volts out to contactor coil. Verif it pulls contactor down, if not replace.
    Then turn on outside disconnect, if it now goes to 120 volts for some strange reason, you know it is from load side of disconnect to compressor and fan.
    Thank you for your reply. I did what you suggested and you are correct. I bypassed the LPS and HPS and went directly to the contactor with 24V and everything seems to work. Except, of course the bypasses switches. I cut the wire ties and searched for a short, separated the wires and made sure that none were touching sheet metal. I then reconnected the 24V properly and got the same result, the contactor sparked when the condenser kicked in. I'm at a loss.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Jul 16, 2008, 07:56 AM
    I think you may have looked at the wrong end. It might be coming from the house side.

    With the tstat wires disconnected and calling for cooling, measure the voltage to the house side of the unconconnected t-stat wires. Also try measuring voltage from these wires and ground.

    Is there a possibiility that Low and high voltage wires were run together in the same conduit?
    OttoPilot's Avatar
    OttoPilot Posts: 3, Reputation: 1
    New Member
     
    #5

    Jul 16, 2008, 12:02 PM
    Quote Originally Posted by KeepItSimpleStupid
    I think you may have looked at the wrong end. It might be coming from the house side.

    with the tstat wires disconnected and calling for cooling, measure the voltage to the house side of the unconconnected t-stat wires. Also try measuring voltage from these wires and ground.

    Is there a possibiility that Low and high voltage wires were run together in the same conduit?
    The 24V wires have 25.4 volts from the house when disconnected. Both wires from the house are new, 10/3 and 18/2, and do not run together in conduit.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Jul 16, 2008, 01:37 PM
    Ok, for the heck of it with the tsat wires disconnected and your probes set to read AC from the coil to ground, operate the coil manually. What do you get?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

120v to 240v [ 5 Answers ]

Hello! If anybody could help me with this it would be great. I'm looking at buying a festool saw from america which runs on 120v but tools and electrical equipment in austraila run on 240v. Is there anything I can do to make it work and if so is it going to be a hassle??

Do I need a converter from 240 V to 120V [ 2 Answers ]

HI... Do I need for a converter from 240 Volt to 120 Volt... cuse I have some electrical equipement which is working on 240 Volt.. now I want to use this equipment in the countries with 120 Volt... Do I need for converter or NOT?? reply me on the below email address Email...

Old 120v outlet [ 1 Answers ]

I am beginning to replace some old 120v outlets when I took off the face plate I found I have 3 white wires and 3 black wires. Do I cap two of each and only attach one black and one white on new outlet on new outlet?

120v to 220v? [ 2 Answers ]

I have a boat which is 240v 50 amp and the marina can only get me two 120v 50 amp circuits to me. Can anyone tell me if I can tie two 120v 50amp circuits into one 240v 50amp circuit. It would be greatly appreciated


View more questions Search