    Burnham boiler will not shut down after temp has been reached
    I have a 1987 Burnham ANS-Z21-13 gas, forced steam boiler that will not shut down when the set temperature has beeen reached, and will run all night. I disconnected the thermostat and the furnace continued to run, so it doesn't seem like the thermostat. It does have 2 pressuretrol controllers (1 was replaced by a tech last year). Could it be a bad pressuretrol controller or a stuck relay somewhere?
    Grady White's Avatar
    Grady White Posts: 1,417, Reputation: 59
    Ultra Member
     
    #2

    Oct 17, 2012, 07:26 PM
    It could be either. Look at the setting on the pressurtrol with the higher set point & also at your pressure gauge. Is the boiler pressure higher than the setting?
    AidanS's Avatar
    AidanS Posts: 2, Reputation: 1
    New Member
     
    #3

    Oct 18, 2012, 02:59 PM
    Yes. Pressuretrol is at 0.5 PSI and the pressure gauge is at 3 PSI. For the past few years that I've owned the house, the Pressuretrol has always been at the lowest setting of 0.5, but the pressure gauge usually sat at about 0 or maybe 1 PSI.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Blower fan on carrier model 50 ez won't shut off when desired temp. Is reached [ 0 Answers ]

Hi I have installed a carrier model 50 ez package unit. My fan blower motor will not shut off when the desired temp. is met. I can bump it up 3 degrees and it will shut off. The problem I have is whenever I set the temp. lower and it gets to that temp. everything turns off but my fan blower motor...

Thermostat will not shut off when desired temp is reached. [ 1 Answers ]

I live in a mobile home have 3 ton carrier unit... ac continues to run when inside thermostat reaches desired level.

Trane heat pump fan continues to run when temp set is reached shuts off if lowr temp [ 0 Answers ]

When on heat and temp set is reached the fan continues to run cold air. Fan will shut off if temp set is lowered 2 degrees. Heat pump is Trane, thermostat is digital white rogers . A similar system, less BTU, shuts off when temp reached.

Furnace fan won't shut off when temp is reached [ 4 Answers ]

I have a 2001 Tempstar DC90 Ultra High Efficincy furnace ! The problem is that the fan will not shut off when the desired temp. gets reached?? I have it set for 70 degrees and it lights up heats up gets to 70 degrees flame shuts off but fan keeps going?? I turned off and reset everything multiple...

A/C won't shut off once desired temp is reached [ 5 Answers ]

I recently changed out my old mercury thermostat to a Honeywell RTH3100C digital non-programmable thermostat. The issue I'm having is that once the desired temperature is reached on the thermostat the a/c won't shut off. What could be the issue?:(


View more questions Search