    Burner does not fire up when heat turned on
    Hi, I have a Lennox Furnace, when you switch on the thermostat to heat and adjust the temp. accordingly, the burner does not ignite. Pilot flame is working, fan works. But no flame on the burner.
    Here is how the thermostat is wired (Is it right? )
    RC- blue wire,
    G- black wire
    Y- red wire
    W- white wire

    UPDATE... Thanks people for your input... the thermostat did not have a jumper cable for `rc-rh` put one on and `presto` done deal
    It`s all good... thanks again...
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #2

    Oct 6, 2007, 05:39 PM
    These wires are not connected as normally it may be some one changed the thermostat and did not connect them properly, the "w" terminal is for heat , the "y" terminal is for cooling, the "g" terminal is for the indoor fan and the red is the wire from the transformer that connects to the "rc/rh" The rc is for cooling and the rh is for heating, if you have one transformer then you put a jumper wire between the rc and rh and connect the red wire to either one.
    The lettered terminals correspond to the color of wires. Y is yellow but in your case some one has substituted a different color wire, go to your furnace and look to see what color wire from your thermostat goes to the outside unit .Good luck, Mike
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #3

    Oct 6, 2007, 06:31 PM
    You should have R, G, Y, and W at the furnace too. Although it is easier to understand if the red wire is on R and the yellow on Y, the important thing is to have the same wire connected to R at the furnace connected to RH and RC at the thermostat.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #4

    Oct 6, 2007, 07:17 PM
    If the cooling worked with the thermostat wired this way than the heat should also. Turn the power going to the furnace off and then back on this will reset the control board. Turn the T-stat back to heat and see what it will do.( Did you change out any parts or thermostat?)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

NO HEAT! Janitrol heat pump and AC system. Changing to Lux Thermostat. Wiring issue. [ 11 Answers ]

I have a Janitrol A/C and heat pump system. I replaced the thermostat with a Lux T9000LC The A/C works fine, but the heater does not. I have it wired as follows: G - Green Y - Yellow W - White RH - Pink B -

GFA Heat; Poor Heating in Apt - Heat is Trapped Near the Ceiling [ 6 Answers ]

In a nutshell: The warm-air registers in my apt are at the very top of the ten foot high walls. Hot air does not circulate properly to heat my 1-bedroom apartment. Details: Based on what I know about the basics of energy, heat rises. And I can't for the life of me understand who thought...

New thermostat, Furnace ignites fire but no heat [ 3 Answers ]

Hi My furnace and thermostat was working fine until two weeks ago. So I replaced the thermostat and the heat started working for the first day then it stopped. I tried to turn up the degrees on the thermostat and I checked the furnace. The electric ignitor was working fine and there was fire...

No Fire/Heat [ 1 Answers ]

Hi. Carrier 8000 2 speed, 580 uXT 100-16 80% AFUE Natural Gas, Installed in 1996 normally runs like a champ. Last week this happened and I just reset and it was good to go. Last night husb left cold air intake grill covered and this morning I noticed I heard the fan cranking but no forced...

Cd burner [ 3 Answers ]

all right I don't know if this is the right section but I just got a cd burner from a friend and I need to hook it up to my computer. Somehow?? Its just the little box where the cd goes.its a BURN- proof 16x10x40x. On the back it has all these little prongy thingys that say: digital audio,analog...


View more questions Search