    Bryant 340MAV furnace
    When it is done the heat cycle and around 10 to 12 minutes after the flame goes out the flame rollout switch will go open, triggering a code 33 and then to code 13. Reset the switch and everything is good. If I leave the front access panel of it will operate fine. Any answers.
    parttime's Avatar
    parttime Posts: 1,440, Reputation: 113
    Ultra Member
     
    #2

    Dec 26, 2015, 05:09 PM
    Hi Don and welcome, sounds like your furnace is over-heating, has the filter been changed? Vents all open? Duct work in good shape?
    Don3491's Avatar
    Don3491 Posts: 3, Reputation: 1
    New Member
     
    #3

    Dec 26, 2015, 06:09 PM
    Took the filter out, checked all vents, cleaned burner tubes & orfices, replaced flame rollout switch. Everything works as it should if I leave the front access Panel off. Put it back on the rollout switch will open about 10 min after the burners shut in and trigger a code 33 & 13.
    parttime's Avatar
    parttime Posts: 1,440, Reputation: 113
    Ultra Member
     
    #4

    Dec 27, 2015, 03:51 PM
    Hi again Don, have you watched as the furnace does a cycle and shuts down? How long does the fan run after the burners quit? Can you post a picture?
    Don3491's Avatar
    Don3491 Posts: 3, Reputation: 1
    New Member
     
    #5

    Dec 27, 2015, 04:44 PM
    Fan is still running when it goes to code 33. Checked the temp on the burner flues and the one next to the rollout switch is 90 - 100 F hotter than the rest. Made an orffice that is 1/8 in bore, original one is some where between 1/8 & 5/64 and it seemed to have cured the problem. Installed it in the first port up stream of the gas valve in the manifold as that is the flue that was the hottest.
    parttime's Avatar
    parttime Posts: 1,440, Reputation: 113
    Ultra Member
     
    #6

    Dec 27, 2015, 05:08 PM
    Well that's a new one on me, good luck and be safe.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Bryant 340MAV Fires and shuts down goes into code 34 [ 1 Answers ]

System cycles properly, Blower runs 90 seconds, gas valve opens, ignitor glows, gas ignites, nice Blue color, shuts down in 3-4 seconds, code 34 blinks on " ignition proving failure, furnace relights, does same thing and goes into Lockout. Tried re-setting Temp rollout safety switch. Could it...

Bryant 340MAV Blower Motor [ 0 Answers ]

I have a Bryant 340MAV that the blower motor when bad in. I had a technician come out and replace the motor. The new motor does not seem to blow as hard. The first tech I talked to on the phone said that the OEM motor is a 3 speed motor. I am not sure but I think the replacement motor is a single...

Bryant 340mav trouble codes [ 5 Answers ]

Bryant 340MAV giving trouble code 33. We replaced the filter - shut off the power for 30min to reset the code- worked for about 6 hrs. now it is showing code 33 again. Blower works, but heat won't kick on.

Bryant 340mav furnace? [ 1 Answers ]

Furnace will fire up and run about 15-20min and I get a burnt smell through the registers. The furnace then shuts itself down. If I shut off all power to the unit and then flick the igniter switch a couple of times, the unit will fire back up and do the same thing all over again. Any ideas?

Bryant 340MAV Code 33 [ 0 Answers ]

Hi, I noted an intermittent heat issue with this model. I replaced a very dirty air filter. Now I get code 33. It would seem as though I am locked out. How do I perform a manual reset on this unit? I tried pushing the button on the rollout, but it doesn't seem to depress (very far...


View more questions Search