    Blower won't turn off trane xe90
    I have a trane xe80. Approximately 13 years old. Heater will come on but occasionally the blower will not turn off after the heat turns off. The light flashes five times. Code indicates flame sensed after gas valve shut off. Could this be caused by inadequate air flow? I have a merv 11 filter at air inlet. Furnace has electronic air filter that was dirty but has now been cleaned. Furnace worked OK for several days after cleaning electronic air filter but malfunctioned again yesterday. I removed merv 11 filter and put in merv 8 but have not tested yet. Thanks for any help.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Nov 4, 2009, 05:21 PM
    This condition is pretty rare. Either the gas control is sticking open or the gas valve relay on the circuit board is sticking closed. You will need a voltmeter to rule out the board... got one?
    stx1100's Avatar
    stx1100 Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 4, 2009, 10:12 PM
    Thanks for your response. I assume the board will need to be replaced if the problem is the gas valve relay? Sounds expensive.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Nov 5, 2009, 02:16 AM
    Quote Originally Posted by stx1100 View Post
    I assume the board will need to be replaced if the problem is the gas valve relay? Sounds expensive.
    You are correct on both counts - IF the problem is the GVR. That's where effective troubleshooting comes in...

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Trane XE90 blower issues [ 1 Answers ]

I'm staying at my mother's house while she is out of town. I decided to turn on her airconditioner and the blower wouldn't work. The compressor outsite works just fine. She has a trane xe90. We've had quite a bitof rain lately, and noticed that the water got up about 6 inches in here...

Trane heat/air not turn off [ 1 Answers ]

I have trane heat/air unit installed in the attic of my house. The problem is when I turn off the air or heat on the thermostat, the ftrane urnace in the attic is still blowing air it sounds like it is still running. Any solution? HELP!! The good thing is that when I turn ON heat or air by the...

Trane xe90 makes clicking and won't heat up to temp setting. [ 1 Answers ]

I have a trane heating system and I have already clean the flame sensor and replace the thermostat. The unit its set at 70 but it will only bring temp to 63 max. The burners will light up and then shutdown when the fan starts. Then, minutes latter the burners will come on again. I noticed that the...

Trane blower fan [ 3 Answers ]

Happy 4th of July all but me!! Lol Last saturdy,we lost power to the house, when it came back on everything worked fine. EXCEPT... the blower on the ac won't stop running.the compressor and such cycles like it should, but the fan will not stop rgaurdless of the switch on the tstat{auto or on...

Quote on 2 1/2 ton Trane XR13 and var spd Trane Blower [ 2 Answers ]

I was just quoted on a 2nd floor A/C replacement, condenser and var speed blower, 2 1/2 ton Trane XR13 with upgrade options. Live in CT Are these prices sane ? Includes removal of old unit, upgrade of refrig line, added insulation on old ductwork - work to be done in walkup attic Quote...


View more questions Search