    Blower will only work in Heat, not Fan-On or Cool-Auto
    Hi, I have a York system about 10 years. Its control board keep giving me problem. Most last year was the connection problem of the socket where the t-stat's 4 wires go in. I finally soldered a fly-wire for the W for heating issue last winter to fix it.

    Now, the summer comes and the cooling is not working. I doubled checked by shorting the R-W, the heat went on and the blower went on, everything is fine. By shorting R to G or R to Y, there was some flowing fluid noise inside the furnace, the external compressor went on and cool, but the blower will not work.

    The R-G connection doesn't turn on the blower, yet it seems to turn on the compressor, or at least some fluid is running through the furnace.

    How can I be certain it is the blower or the board has problem? The blower had replaced a cap last year when R-G didn't do anything including the fluid noise, yet R-W nor R-Y can make the blower run.

    Thanks!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    May 27, 2008, 04:20 PM
    A/C blower relay on board is probably defective.
    jiaoniang99's Avatar
    jiaoniang99 Posts: 2, Reputation: 1
    New Member
     
    #3

    May 28, 2008, 07:48 AM
    Thanks for your quick reply. If so, is changing the relay a feasible solution or the whole board?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    May 28, 2008, 08:07 AM
    Whole board. The relay might be impossible to find then you are still going to have to plat with a printed circuit board. Not a good thing. Get the board.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Blower won't come on in auto mode. Heat only [ 2 Answers ]

Carrier 48SB-030080301 1990 model nat gas. On a/c mode works fine. Heat- burner lites but blower will not come on at all unless on manual. I changed the J2 jumper on thermostat from hg to he to see if I could get by for a while and its been working for about a month now. Other than blast of cool...

Blower won't run in auto for heat with oil furnace [ 9 Answers ]

I have an oil furnace. A/C works fine. Heat last season worked fine. Started up furnace this year just fine. But blower would not start on auto. The blower will run in heat mode when set to On. I replaced the Limit Switch in the Plenum. No change.

Blower does not work in Auto [ 1 Answers ]

Ihave an older electric forced air heating system. With the system in heat the blower will not run in the auto mode. The heat does seem to work, it will heat the house. During the airconditioning season it worked fine. During the A/C season I didhave to change a relay. I wired it IAW the...

HEAT-OFF-COOL system switch - AUTO-ON fan switch [ 1 Answers ]

From an Email: ''Dear asklabman, I am a first time house ownere & having an issue with my Honeywell T8112 Programmable Thermostat. Thermostat has two switches for the fan - AUTO FAN & FAN ON switches and three switches for thes system, COOL, HEAT & System OFF modes. Yesterday we turned ON...

Fan Blower doesn't come on in Fan,heat or cool [ 2 Answers ]

Yesterday I turned on my heat(coil in air handler) and everything worked fine. Last night I turned it on again and the fan wouldn't come on no matter where the switch was: fan only, heat or air. I made the appropriate temp changes for heat/air. There is a humming noise coming from the heating coil...


View more questions Search