    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #1

    Dec 23, 2008, 11:46 AM
    Blower not working when a/c is turned on
    I turn on the heater and everything works fine, I turn the fan to ON and everything works as it should, but when I turn the a/c on the only thing that happens is a noise from the unit like fluid running through it however the blower does not start, this is with the blower in the ON position and the heat off a/c switch on OFF, however as soon as I switch to a/c the blower turns off and it makes the same noise mentioned above. I have tried to jumper r-g, r-w, and r-y with the same results
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #2

    Dec 23, 2008, 11:53 AM

    What type of thermostat? Sounds like a case of bad switch contacts.
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #3

    Dec 23, 2008, 11:59 AM
    Thermostat is a Ritetemp model 8035c. I thought the contacts were bad as well, but when I jumper the contacts at both the thermostat and the unit the same thing happens
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Dec 23, 2008, 12:03 PM

    Okay, give us a li'l more info... system type, brand and model #'s. etc.
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #5

    Dec 23, 2008, 12:08 PM
    Lennox Elite Series G24M4/5-100A-12. Gas furnace, not to familiar with HVAC systems, so don't quite know what info you are looking for
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #6

    Dec 23, 2008, 12:17 PM

    When you jumpered/un-jumpered R-Y, did you see a rather large/bright spark? If the outdoor unit contactor coil is partially shorted, it could be hoarding control voltage while still functional.
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #7

    Dec 23, 2008, 12:22 PM
    It does not spark at the thermostat, but it does at the unit, but I would not call it a large/bright spark
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #8

    Dec 23, 2008, 12:26 PM

    Try this: disconnect wire from R at indoor unit, then with R-G jumpered, jump R-Y. What happens?
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #9

    Dec 23, 2008, 12:29 PM
    With R disconnected won't I simply be jumping G-Y?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #10

    Dec 23, 2008, 12:30 PM
    Quote Originally Posted by KC13 View Post
    Try this: disconnect wire from R at indoor unit, then with R-G jumpered, jump R-Y. What happens?
    Re-read and follow as posted.
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #11

    Dec 23, 2008, 12:49 PM
    At the indoor unit with R disconnected and R-G jumpered, then jumping R-Y the same thing happens, the blower is on with r-g jumpered then when I connect r-y it turns off and the only sound left is the small wooshing sound. The spark you previously mentioned, while I still wouldn't call it big, it is much bigger than than anything I get from r-g
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #12

    Dec 23, 2008, 01:16 PM

    I would check the outdoor unit contactor coil - see if it looks burned. The test you just performed is strengthening my "hoarding" theory... disconnect power to outdoor unit first.
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #13

    Dec 24, 2008, 09:43 AM
    How do I locate the contactor coil and what does it look like?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #14

    Dec 24, 2008, 01:38 PM

    It is the primary control relay for the outdoor unit. If you disconnect the power supply and remove the control compartment cover, the incoming power supply wires should take you right to it. The coil is the fine winding usually visible near the base. Ideally, a check of the coil resistance and/or amps is the sure thing, but if it appears obviously burned no test is necessary.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #15

    Dec 24, 2008, 02:21 PM

    Its to cold for a/c
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #16

    Dec 24, 2008, 02:28 PM
    That wasn't the question now was it, and how do you know it's too cold do you know where I am?
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #17

    Dec 24, 2008, 02:42 PM

    Smile,be happy,a little humor and Christmas cheer goes a long way,, Baa Humbug, I hate it when people can`t take a joke,, I`ll remember your name in the future,:(:(
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #18

    Dec 24, 2008, 03:11 PM
    Quote Originally Posted by drchef View Post
    That wasn't the question now was it, and how do you know it's too cold do you know where I am?
    If it's a/c you're needing right now, I'm jealous...
    drchef's Avatar
    drchef Posts: 9, Reputation: 1
    New Member
     
    #19

    Dec 25, 2008, 12:14 AM
    New Orleans-It snowed here for the second time in 30 years and two days later I was in shorts

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Blower not working and blower running all the time [ 2 Answers ]

I have a Lennox electric furnace that's about 10 years old or so, the elements come on but no blower. There is a summer fan switch that will make the blower run when switched on, but it will not come on with a call for heat. Also at my work, there is a york gas pack that is probably 15 years old....

Blower not working [ 4 Answers ]

I have a Carrier Weathermaker 8000 furnace and recently the blower does not run. I noticed that when I set the Thermostat from AUTO to Run the Fan does not come on a faint click can be heard. What is the best way to troubleshoot this issue? I suspect the issue is with the cirucit board or...

Heat and Air not working on Attic unit, but blower working. [ 1 Answers ]

The blower is working fine on our Heating and Air Conditioning unit but neither the Air or Heat will work. The emergency Heat works fine though. The unit is a Carrier with the words American Standard written on the outside fan unit. What should I look for before calling a tech or what would this be...