    vegasbusa's Avatar
    vegasbusa Posts: 4, Reputation: 1
    New Member
     
    #1

    Oct 29, 2009, 06:46 PM
    My air handler fan does not turn on
    In A/C mode, the comppressor turns on , but the fan will not. In heat mode, nothing happens, I'm thinking because the fan needs to run to withdraw the exhaust from the gas. If I turn the fan switch to "on" still have no fan. I have a digital thermostat Any help out there. Thanks in advanced.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #2

    Oct 29, 2009, 06:58 PM
    Did you try turning the fan to the on position on the thermostat to see if the blower would work? If so and it didn't. You can jumper the R and G circuits on the thermostat to see if the blower runs. If no blower jumper R and G at the blower section. If no blower its time to pull out a voltage meter to find out why or give us a make and model to try and help.
    vegasbusa's Avatar
    vegasbusa Posts: 4, Reputation: 1
    New Member
     
    #3

    Oct 29, 2009, 07:21 PM
    I put it in the "on" position and still nothing. I have about 27 volts from R to ground. When I make it call for heat, I get 27 volts at the G and W terminal. The led flashes like it wants to do something, but nothing happens. I jumped out the R and G and I hear something going on but the fan does not turn on. Thanks
    jaxbchjim's Avatar
    jaxbchjim Posts: 1, Reputation: 1
    New Member
     
    #4

    Nov 12, 2009, 05:33 PM
    Same problem here - what was the solution?
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #5

    Nov 12, 2009, 07:25 PM
    Ask a new question, include brand/model#...
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #6

    Nov 12, 2009, 08:58 PM

    It is very possible that you have a problem with the motor. Use a volt meter at the connection where the motor wires conncet to the wires from the circuit board and check across the White wire and the Black wire while the unit is calling for cooling at the thermostat.

    Make sure that door switch is compressed.

    Also you could tell us what happens when you turn the thermostat to heat, things like does the inducer motor come on and does the hot surfice ignitor glow and does the burners come on.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Lennox heat turn off and turn back on to work [ 2 Answers ]

I have a lennox heater I have to turn it off and turn it back on to get it to heat. What is wrong and how do I fix it.

Central Air, Handler Fan will not turn without a helping push [ 6 Answers ]

I have a Lennox, 10 year old central air unit in my condo. The Air Handler Fan is not turning on as it's supposed to. I opened the unit and gave the fan a spin, and then it worked fine but still will not start on its own. I put the fan on manual and just letting it run, and that's keeping the...

Heat blower does not turn - Air Handler does not turn on for heat [ 7 Answers ]

I have an Energy Kinetics System 2000 boiler. It is hooked up to two different zones (two different air handlers). Zone 1 (main house) when turned on at the thermostat clicks and calls for heat, the boiler starts for a bit but the fan/blower never kicks on. Zone 2 (master bedroom) works just...

My a/c runs when I turn it on but my air handler does not come on. [ 1 Answers ]

My a/c runs but my air handler does not come on. I checked the breakers on the breaker panel and they are not tripped. The house is about 5 years old. Eric

Turn outside faucet 1/4 turn to the side so the hose won't be bent [ 6 Answers ]

Can I safely put a pipe wrench on an outside faucet and on the pipe it is attached to and turn it one quarter turn to the side so the hose connected to it won't be bent and spray at the attachment?


View more questions Search