    Ac unit not working
    Ac is not running outside. Fan is running in house but nothing is running on the unit outside. Have already replaced the fuses in the plug and the contacter. Any suggestions?
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Aug 9, 2015, 03:00 PM
    Fuses in what "PLUG"? No plug on a hard wired AC. Tube fuses in the pull block? Have you ever measured voltage at the unit? Are you getting voltage to the contactor? There should be an outside disconnect as that is code. Is there voltage at the hot side of the disconnect. There should be 24 VAC at the contactor and 240 VAC at the disconnect.
    lucie_25's Avatar
    lucie_25 Posts: 3, Reputation: 1
    New Member
     
    #3

    Aug 9, 2015, 03:18 PM
    Quote Originally Posted by ma0641 View Post
    fuses in what "plug"? No plug on a hard wired ac. Tube fuses in the pull block? Have you ever measured voltage at the unit? Are you getting voltage to the contactor? There should be an outside disconnect as that is code. Is there voltage at the hot side of the disconnect. There should be 24 vac at the contactor and 240 vac at the disconnect.
    Yes, the tube fuses in the block. Sorry I did'nt know what to call it. Ok.. My husband just checked it and 240 at disconnect and nothing at contactor.
    lucie_25's Avatar
    lucie_25 Posts: 3, Reputation: 1
    New Member
     
    #4

    Aug 9, 2015, 03:33 PM
    Quote Originally Posted by lucie_25 View Post
    yes, the tube fuses in the block. Sorry i did'nt know what to call it. Ok.. My husband just checked it and 240 at disconnect and nothing at contactor.
    Can you tell me what this means? Pleeeaaassseee! Lol
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #5

    Aug 9, 2015, 06:32 PM
    With the thermostat at cooling and the temp lowered so it is calling for the AC to run, you should have 24VAC across the contactor and you should hear the contactor "snap". You should then also have 240 VAC on the compressor input. The contactor is basically a relay to allow current across the terminals. Since you replaced the contactor, it is probably not the issue. I would look on the control board of the HVAC unit to see if there are any trouble codes-look for a blinking light and count the blinks. The codes are almost always on the inside of the air handler(inside fan). Also look for any broken wires at the condenser, weed-wacking can cut them.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

AC issue, outside unit working, blower fan not working [ 0 Answers ]

Hi, newbie here. My AC is having issues: the outside unit is working, but the blower fan is not. So I tested it out with these findings: 1. Normal condition: Ctrl - cool, Fan - auto, as stated above; 2. Ctrl - off, Fan turned to on, fan is working (air coming out from vent); 3. Then turned...

AC outside unit not working [ 7 Answers ]

Hello, I do not have a good knowledge of electricity or appliances. Before I cal a HVAC technician, I wanted to see if there is something I could do. It is the middle of summer here in Texas and we have no AC! Could really use some help and it is a Sunday as well. Problem: When I turn the...

Outside Unit Not Working [ 4 Answers ]

Our outside heat pump unit is not running. The thermostat was replaced recently (5 times!). Can a problem with the thermostat effect how the outside unit works? What should we be looking at to figure out what is going on?

Rheem-heat-pump-outside-unit-humming but blower unit working [ 3 Answers ]

I have a heat pump and ac unit outside. The inside blower fan still working but the outside unit humming. Are there any quick fixes here

Heat and Air not working on Attic unit, but blower working. [ 1 Answers ]

The blower is working fine on our Heating and Air Conditioning unit but neither the Air or Heat will work. The emergency Heat works fine though. The unit is a Carrier with the words American Standard written on the outside fan unit. What should I look for before calling a tech or what would this be...


View more questions Search