    coloradojohn's Avatar
    coloradojohn Posts: 2, Reputation: 1
    New Member
     
    #1

    Jul 28, 2008, 09:43 AM
    With AC on blower fan runs then stops
    My problem is that the air conditioning unit (Trane) runs fine however when the blower turns on it will run for 25-30 seconds and then turns off for 60-90 secords before turning on again. If I run the furnace the blower operates as expected. One service company has indicated that it sounds like a winding on the blower fan motor has gone bad causing this intermitten cycling to occur and suggest replacing the motor. Has anyone had a similar problem or heard of something like this that could confirm their findings or dispute them. Thank you for your help!
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #2

    Jul 28, 2008, 10:30 AM
    Check the capiciter,, they only cost a few dollars much less than buying a new motor,if the winding is bad in motor I don`t think it would run at all,not even a little bit.. if you don`t have the means to check capiciter take it to a electric shop and have it tested
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #3

    Jul 28, 2008, 11:00 AM
    My problem is that the air conditioning unit (Trane) runs fine however when the blower turns on it will run for 25-30 seconds and then turns off for 60-90 secords before turning on again. If I run the furnace the blower operates as expected

    If you run the furnace and the blower operates normally it is probably not the motor or capacitor But something in the A/C circuit. It could be the control board or your thermostst.

    What is the model number and brand of your thermostat?
    coloradojohn's Avatar
    coloradojohn Posts: 2, Reputation: 1
    New Member
     
    #4

    Jul 29, 2008, 07:47 PM
    Quote Originally Posted by hvac1000
    My problem is that the air conditioning unit (Trane) runs fine however when the blower turns on it will run for 25-30 seconds and then turns off for 60-90 secords before turning on again. If I run the furnace the blower operates as expected

    If you run the furnace and the blower operates normally it is probably not the motor or capacitor But something in the A/C circuit. It could be the control board or your thermostst.

    What is the model number and brand of your thermostat?
    wmproop's - it's a Honeywell model tb112d1005 or pf1a, sorry but the prior owner installed and there are no obviouse markings on the unit. Thank for your help!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Jul 29, 2008, 08:42 PM
    Sorry no numbers in Honeywell factory list matches the numbers you provided.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Blower fan runs and stops runs and stops [ 4 Answers ]

I have a heil system and when it is on Heat or Cool the blower runs for about a min and then stops for a min. And continues running like that. The main system that is outside (condenser I quess its called?) keeps running. It is just the blower in the furnace in the garage. I had a company look at...

AC Inside Blower Stops, Condenser runs continuously Until Entire Unit shut off & Reset [ 6 Answers ]

I have a Trane compressor outside. The unit comes on and the interior blower comes on for a few hours and then stops blowing. I tried to turn on the fan via the thrmostat and it does not work when it shuts down but otherwise works fine so its not a wiring problem. The outside unit continues to...

Water runs for 30 seconds and then stops running [ 8 Answers ]

For 5 days now whenever we turn on a faucet the water runs as expected for maybe 30 seconds and then just quits running. This is happening in the kitchen, shower, washing machine, basically everywhere in the house. We live outside the city limits and just recently started receiving 'city' water...

Hot water runs for a minute and then stops [ 3 Answers ]

The hot water in the house for a minute and then stops.I have a mixer tap which I take the top off and blow back the hot water for a minute.The hot water runs again for a minute then stops.There is no banging in the pipes or any noise ,and the hot water system is full


View more questions Search