    agroleau1's Avatar
    agroleau1 Posts: 1, Reputation: 1
    New Member
     
    #1

    Dec 7, 2009, 08:48 AM
    3 wire thermostat install, heating only, boiler, with automag valves
    I am trying to hook up a 3 wire (red,green, and white) thermostat. The old thermostat was an automag mercury type that says r+b heat only. All three wires where hooked up. I installed and now my heat will not shut off upstairs. I have 4 zones. I used same thermostat downstairs. Seems to be working fine. I have red to rb jumped to rc, green to w and white to y.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Dec 7, 2009, 09:06 AM
    You have a old Automag zone control system. See the Automag company below.

    You can add there relay or similar to make your 3 wire zone valve work.

    CNV84 Relay
    Relay to adapt existing 3-wire thermostat system to 2-wire thermostats. (One relay required for each thermostat.)

    OR you can just replace the valve head (I recommend this instead of a relay)

    Call them. They have been around a long time and are very knowledgeable. Many years ago I installed a bunch of there stuff on contract jobs for the US Government.

    Automag division of KCI Industries, Inc.
    Manufacturer of "Fail-Safe" normally open Zone Valves

    1111 Hill Street, Jessup, PA 18434
    (800) 451-2002
    (570) 383-2428
    FAX: (570) 383-9820

    Web site loaded with info.

    AUTOMAG

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

3 Wire Thermostat Install? [ 4 Answers ]

Hi All, I'm trying to replace my old mercury thermostat (from 1979 it seems) with a new 4+1+1 thermostat. I took off the old 'stat and I had 3 wires connected to it brown, green(maybe grey), and black. The brown and green wires were connected to the same terminal while the black one was...

How to install 2-wire thermostat [ 1 Answers ]

We had an old (1950's) manual thermostat. Upgrading to a Honeywell rth7000 programmable thermostat. We have oil heat only. I have two quesitons; 1) Am I correct in assuming that we connect one wire to R (is it R or RC, I think we have both) and one to W? 2) Will this allow the programmable...

Domestic Hot Water Heating Boiler System Rad Valves [ 3 Answers ]

Re hot water boiler heating system,with 3 zone valves,in home.need to know to know about small "automatic"? Vents at ends of rads One was 'leaking']slowly but steadilty.and dripping slowly thro to basement forming small 3 inch mark on floor. 4 years ago these "automatic" valves replaced (from...

Hot water but no heating! Vokera boiler and honeywell cm67 thermostat [ 1 Answers ]

Please can someone help? I have recently moved into a home with a Vokera Boiler Linea range and honeywell CM67 thermostat. When we first moved in we had hot water and heat. With the hot weather the boiler has been on hot water only for approx 2 week. This week we have gone to put it on hot water...


View more questions Search