    Wires in emt
    How many #12 wires in 1/2and3/4 metal tubing emt.allowed.
    cyberheater's Avatar
    cyberheater Posts: 321, Reputation: 12
    Full Member
     
    #2

    Sep 18, 2009, 10:44 AM

    It would be different for different conduit types because each different material has it's own ID
    Size. Remember to check with your local codes as well.
    Here's a link that might help you for this question and more. Designing Conduit Runs -- calculating fill factor, sizing conduits, fill factor, designing conduit runs, electrical metallic tubing, 569 compliance, conduit bends.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Sep 19, 2009, 04:49 AM
    You are specific with the conduit type being EMT. Before knowing how many wires can fit in any conduit, the type of insulation must be known, as each insulation has different outside diameters.

    The most popular wire now is THHN/THWN, and according to the NEC 2008 Edition Annex C Table C1, 1/2" EMT can take 12-#14 and 9-#12, 3/4" can handle 22-#14 and 16-#12.

    While this gives the max wires allowed, this brings up another issue to be concerned with, derating of the ampacity of the current carrying conductors. This can be accomplised by increasing the size of the conductors, which will affect the wire fill of conduit and may require a larger conduit, or using a smaller size fuse or circuit breaker.

    As there are many variables and calculations to consider, all the details are needed to be able to size a conduit run. Just because a 3/4" EMT can handle 22 #14 THHN wires, does not mean that all 22 #14 wires can be current carrying and protected with 15 amp breakers.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

230 volt welder with 2 wires outlet with 3 wires. [ 7 Answers ]

Hello. I have an older stick welder that has a ground, white wire and black wire. The outlet I have to connect to has a ground, black, white and red wire. Is there a way I can connect the old welder to the newer wires? I know the red and black are hot but what about the common white wire? What...

3 wires + 2 wires  POOL MOTOR [ 2 Answers ]

I need help connecting a motor for my pool. The motor has 3 wires coming out of it. 1 white, 1 black, 1 black with a white stripe. A continuity test on the 2 blacks says they are wired together somewhere. I have a power cable coming out of the ground. 1 white + 1 black cables inside. ...

Thermostat Wires - Only 2 Wires (both black) [ 4 Answers ]

Hi there, I'm switching my thermostat for a newer digital one, though when I took out the old thermostat, there were only 2 black wires with white stripes on them. The new thermostat calls for an RH wire and a W wire, but I have no way of distinguishing the two apart. How can I tell which wire...

Hampton Bay remote wires do not match fan wires [ 1 Answers ]

Yesterday I installed a new Hunter ceiling fan. I also purchased a Hampton Bay wireless wall switch. Everything went well until I wired up the remote receiver. The receiver has a blue wire for the light that is supposed to connect to the blue wire (light) from the fan. The Hunter fan does not have...


View more questions Search