    Wireing for a 60 amp sub Panel
    I'm installing a 60 amp subpanel 10 feet away from my main 200 amp service. I ran #6/3 copper to the sub panel. I understand that I have to not use the green screw that connects the neutral buss to the metal case. And I should connect the bare copper to the case and the white neutral to the neutral buss in the sub panel . My question is how do I hook up the bare copper and white neutral wires in the main panel? Thanks Rob
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Feb 10, 2011, 07:51 AM

    The bare (grounding conductor) is connected to the ground bus. Hots are connected to the breaker and Neutral is connected to the Neutral bus.

    At the sub panel these two (Neutral and Ground) must be isolated from each other.
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #3

    Feb 10, 2011, 08:19 PM
    IN most cases your main panel will have a neutral buss which is also the grounding bus. If this is the case, you will connect both the neutral and the ground to this buss. However, in the sub panel these must be kept separated. You will need a grounding buss in the sub panel separate from the neutral buss. The grounding buss will be bonded to the panel, and the neutral buss will NOT be. You must use a grounding buss, not just connect it to the case, since all of the circuit grounds will be connected to the grounding buss separate from the neutral.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Updating service panel to 200 amp with feeder to 100 amp panel in old house [ 8 Answers ]

I currently in the process of converting 1000 sq ft of attached garage into living space while doing this we are updating electrical service to 200 amp new service, there is 100 amp service in the old part of the house which will remain but need to be sub paneled from the new 200 amp service. I...

200 amp panel feeding a 100 amp panel roughly 130' away [ 7 Answers ]

Hi all, We are building a apartment above the garage,my question is what size wire do I need to run from the 200 amp panel to the 100 amp panel roughly 130' away? I want to use aluminum wire as I think copper would be to costly. Thanks for your help in advance, Dude :eek:

Can I put a 150 amp breaker in a 200 amp panel to feed a 150 amp sub panel? [ 8 Answers ]

Can I put a 150 amp breaker in a 200 amp panel to feed a 150 amp sub panel with a 200 amp service?

100 amp panel to new 200 amp panel and sub panel [ 3 Answers ]

I have a very small (1000sq feet) 1920 home in Northern New Jersey which 15 years ago was upgraded to breakers with a 100 amp panel. The whole house does have copper romex in it now, and I am adding a substantial addition (3000 sq feet) to the house and I want to put a sub panel in the new portion....


View more questions Search