    Wire sizes
    I recently ran 12-3 wire off a 15 amp breaker as a main feed for my 2nd floor, only problem is it connects to 14-3 at the closest junction box to spread out to all the other connections on the 2nd floor. Is this okay? Also I prob. Only had to run 12-2 anyway as there is no other connection between the circuit breaker and the junction box...
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Sep 23, 2008, 03:55 AM
    It all depends on what the 14/3 feeds. If it splits off into two circuits then yes, you did good by running 3-wire.
    How did you hook it up in the panel? Did you splice it wire for wire in the junction box?
    Who ran the 14/3 and where does it go?

    You should not have run #12, or should I say you did not have to. MAKE SURE you keep it on a 15A breaker. I would out a label on the wire in the panel and mark it "15A ONLY". This way no one later will see a #12 wire and put it on a 20A as is typical.
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #3

    Sep 23, 2008, 08:51 AM
    If anything you have overkill. You might save this Wire sizes, gauges, for breakers
    matt2008's Avatar
    matt2008 Posts: 5, Reputation: 1
    New Member
     
    #4

    Sep 23, 2008, 02:59 PM
    Thanks guys! I just wanted to make sure it wasn't a fire hazard, someone had told me the only thing is the 12-3 wire might run hot and send spikes threw the current, also the junction box I ran the 12-3 into had multiple circuits coming out of it so I figure now that the 12-3 was needed. Im so far ahead after drywalling the 12-3 into the ceiling that it would be eaisier for me to replace the 14 gauge wire now instead of redoing the 12. Also to answer stan I made a short cut down at the panel by tapping the 12 into the 14 that origanlly came out of the panel... kind of rigged right now but I was not comfortable just yet with making connections directly into the panel. That will come later.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #5

    Sep 23, 2008, 03:14 PM
    Quote Originally Posted by ballengerb1 View Post
    If anything you have overkill. You might save this Wire sizes, gauges, for breakers
    I agree!

    I also agree with Stan, make sure you label the wire at the panel.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire sizes [ 16 Answers ]

How do I find out what wize sizes to use for a 100, 150, 200 amps panels?

Tip sizes [ 1 Answers ]

Which tip size should you use for sanding sealer?

Wire sizes and breaker boxes on main lines [ 1 Answers ]

I am currently adding an addition on to my 100 year old house (which has 50 year old wiring). I only have 100 amp service, but this is enough for now. Here is my plan: From the pole to the addition will be a 100 foot stretch of 4/0 cable. I realize that with 100 amp service I do not need that...

Drain pipe sizes and venting sizes [ 4 Answers ]

1.) What dia. Drain pipe is used for the shower/tub? 2" ? Is that ID or OD? 2.) What dia vent pipe is for the shower/tub? 2"? 3.) I'm going to put a vent in for the shower/tub in my basement. It starts at the slab then goes straight up about 7ft. And then does a 90 and then is running...


View more questions Search