    Wire Size
    200 amp socket is 400' from 200 amp panel what size wire?
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Oct 10, 2010, 02:09 PM

    You might want to consider have the power co. put in a transformer and drop.

    Are you going to need 120/240?

    Just using 120Vac to ground, you will need 900 kcmil to get an acceptable voltage drop.

    Have you calculated the necessary load?
    ditka's Avatar
    ditka Posts: 2, Reputation: 1
    New Member
     
    #3

    Oct 10, 2010, 02:36 PM
    We have three power poles on our property that I want to eliminate. The power company quoted $5,000.00+ for a on ground transformer and buried cable.
    I would have to bury 200' from the transformer to the house. Thought it would save me some money doing a run to the pole on the road 400'.
    Yes need 120/240. Have not calculated the necessary load. Thank you
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Oct 10, 2010, 02:51 PM
    Quote Originally Posted by ditka View Post
    We have three power poles on our property that I want to eliminate. The power company quoted $5,000.00+ for a on ground transformer and buried cable.
    I would have to bury 200' from the transformer to the house. Thought it would save me some money doing a run to the pole on the road 400'.
    400' is way too far to go with "standard" size wire. You are going to have to go up in size to go that far.

    IMO I would go with the power company's quote. A transformer closer to the house (250' or less) is a MUCH better installation.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size & conduit size for 60 am subpanel 150 from source [ 9 Answers ]

Indiana question: I want to install a 60amp subpanel 150 feet from the main panel. This is all exposed runs both inside and out in a commercial envirenement. What gauge and type of copper wire and what size conduit whould I use. How often should insert a junction box in the run. John

What size wire do I need to run to get a 100amps. 225ft. using direct burial wire? [ 5 Answers ]

What size wire do I need to run to get a 100amps. 225ft. using direct burial wire coming from a 200amp. Service? Any info. Would be appreciated. Regards, Garry

Wire size wire & circuit breaker do I need for a 15.8 range [ 2 Answers ]

What size circuit breaker & wire size do I need rfor a 15.8 raqnge ?

Sub Panel AMP Size and Supply Wire Size [ 1 Answers ]

I would like to install a sub panel in my garage I was told to run 6/3 Romex to supply the sub panel and have done so. The run is about 65 feet and I am now wondering after reading this site what is the max I can get for this size wire? I plan to supply a compressor (20 amp) and the garden...


View more questions Search