    Wire size for a 100 amp lug sub panel
    Hi
    I have a 200 amp main panel, but it is a small 24 slot panel. It is full and I need to add three more circuits. I want to run a 100 amp main lug subpanel. The plan is to move the clothes dryer breakers to the new sub and use the existing location in the main panel to install a 100amp breaker to supply the subpanel. The sub is going to be about 30 feet from the main. My first question is what size wire do I need to do this. I have been told everything from 6-3g to 2-2-6-8 The heaviest single load I forsee being on this subpanel is the clothes dryer My second question is since they make 200 amp panels with anywhere from 24 to 42 slots (mine being the 24 slot) should I have any concern that I maybe overloading this panel? I can't see a size marking on the SE cable but it looks to be at least .25 inch thick
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #2

    Nov 17, 2008, 08:17 PM

    You may be able to install twin breakers in the main panel, and say forget the sub.

    Twin breakers will help you make some room for the new circuits you plan to install.

    Post your service panel information, and we can tell you if installing twins are possible.

    Also, only you will no if you are overloading the existing service rated panel, by doing a demand load calculation.

    Are your appliances gas or electric? Do you have any heavy players like an electric furnace, tankless water heater, etc..
    utysam's Avatar
    utysam Posts: 3, Reputation: 1
    New Member
     
    #3

    Jan 21, 2010, 05:18 PM
    Cable size 120 mm2 with matching lug
    hermanwachs's Avatar
    hermanwachs Posts: 28, Reputation: 0
    New Member
     
    #4

    Jan 21, 2010, 05:34 PM

    #2 ser is best for this. Easy to use and priced right. Around here the inspector doesn't flinch at a 100 amp breaker, though I've been told the 2008 NEC has it at 75 (?). Use antioxidant and you'll be good.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Jan 21, 2010, 05:52 PM
    Quote Originally Posted by utysam View Post
    cable size 120 mm2 with matching lug
    Judging from his post, unless otherwise stated we have to assume the OP is in the US or Canada.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size for a sub-panel? [ 1 Answers ]

I have a 100 AMP main Service panel in my residence and plan on doing some kitchen remodeling. What size breaker would normally be used in a 100 AMP Panel to feed a sub-panel. Additionally, what size wire would feed the sub-panel from this breaker. I am think a 50 AMP breaker and # 8 wire to...

Wire Size and panel size [ 6 Answers ]

I have a separate small living quarters that is a single room that is about 180 feet away from the main panel. It is going to get another little bed room a small kitchen and a bathroom also maybe a washer. The main panel is a 100 amp meter socket combo. What should I upsize the main panel to? ...

Wire size for sub panel [ 1 Answers ]

Hi, :) We are converting a garage into a guest house, with permits, and I have a few questions on the electrical side. I have tried to search for my questions, but need more info. Plans are to place a 100 amp sub-panel 250 feet from main panel. Will # 2 in 2 inch conduit be enough, how much...

125 amp sub panel 250' away wire size [ 5 Answers ]

I have a 400 amp service in my home and will be running a line to my shop with a total run of 250' to feed a sub panel 125 amp service. What wire size is the 250' run? Would a 100 amp service be the same wire size? I would like to run copper wire, is aluminum that much less expensive? Any other...

100 amp sub panel wire size [ 2 Answers ]

I now have the 100 amp breaker installed in my load panel. I will run wiring from the load panel to a 100 amp sub-panel in an unground 80 schedule PVC. I believe I need to use #2 wire for the hots and the neutral. If this is correct, then what size ground do I use? Number 6? The sub- panel...


View more questions Search