    Wire size for 100 amp 3 phase circuit
    I am installing a commercial convection oven rated as follows: 220V 3 Phase. The oven pulls 23 kilowatts. I calculate this to be about 64 maximum amps. So, I'll use a dual pole GE 100 amp breaker in my box. The wire run will be about 15 feet through conduit. I'm getting conflicting reports on the wire size I need. Am I correct to use #2 stranded copper for the hots and neutral, and # 6 or 8 for the ground? Also, I'm guessing that my only connection options are split connectors and a lot of tape? Are there junction boxes available that have "terminal strips" of sorts to connect the 'line and load" sides into? Thanks in advance. rmwac
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Mar 5, 2009, 04:31 PM
    Are you an electrician? This is not a DIY job you are looking at.

    Is the oven 208V or 240v? There is no such thing as "220" anymore.
    What is the service, 120/208v or 120/240v?
    Are you aware that 120/240v 3 phase has a high leg?

    How are you going to make a 2-pole breaker work fro 3-phase??

    I get 55.5 amps at 240v 3-phase.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size & conduit size for 60 am subpanel 150 from source [ 9 Answers ]

Indiana question: I want to install a 60amp subpanel 150 feet from the main panel. This is all exposed runs both inside and out in a commercial envirenement. What gauge and type of copper wire and what size conduit whould I use. How often should insert a junction box in the run. John

Sub Panel AMP Size and Supply Wire Size [ 1 Answers ]

I would like to install a sub panel in my garage I was told to run 6/3 Romex to supply the sub panel and have done so. The run is about 65 feet and I am now wondering after reading this site what is the max I can get for this size wire? I plan to supply a compressor (20 amp) and the garden...

Cable size for 320 amp service , single phase [ 1 Answers ]

I'm installing a 320 amp single phase service. What size cable do I need to use? I'll be using copper. Also what size for 200 amp?

How am I going to size my 3 phase X'mer with 1 phase load using current as reference [ 3 Answers ]

Hi, I'm Peping: I have 90 pieces of single phase loads with current of 2 Amperes. This will be loaded to a 3 phase transformer, Wye connected having a line to line voltage of 220 Volts. What will be the size of the transformer required for the mentioned loads? Many thanks, Peping


View more questions Search