    Why use #12 wire for outlets and code allows #14 for lighting
    Why do electricians use#12 wire for outlets and the code allows no#14 for lighting
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Jun 15, 2010, 11:09 PM

    12 AWG can be used with a 15 or 20 A breaker. 20 A or 15 A outlets can be used here.

    14 AWG must be used with a 15 A breaker. 15 A outlets must be used here.

    12 AWG costs more. 20 A outlets cost more. 20 A breakers cost more. Certain areas require 20 Amp circuits particularly kitchen and bath.

    Lighting is typically smaller circuits and it's getting smaller with high efficiency lighting. Ceiling fans are still low wattage loads.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Jun 16, 2010, 03:51 AM
    Quote Originally Posted by boatntote View Post
    why do electricians use#12 wire for outlets and the code allows no#14 for lighting
    I am not sure of the actual question here, but both parts of this are wrong, at least in most parts of the US.

    NOT nearly all electricians use all #12 for receptacles. Some areas require all #12 (dumb rule IMO), some areas require 15A circuits for lighting.

    Boat, if you post back a bit more detail about what it is you are actually asking, and why, we may be able to help you.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #4

    Jun 16, 2010, 05:11 AM

    In our Area, we can't use #14, however, some Modulars being shipped in have #14, A Friend of Mine bought one, piss poor wiring.
    Both hall 3 ways have to be on for lights to work.
    When doorbell breaker is turned on, it chimes and stays energized, they wired transformer directly to chime and left doorbell wires disconnected.
    Kitchen Light stays on, no switches turn it off. In the baths, 1 switch works light and fan, other switch does nothing.
    Never seen so many problems in one house.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #5

    Jun 16, 2010, 10:13 AM

    To be honest with you, if an electrician can use 14 AWG cables or individual conductors, they will do so. It is cheaper to purchase 14 AWG than 12 AWG cable.

    While there are some mandated 20A circuits (kitchen counter tops) general lighting and receptacles are still calling for 15A.

    If I take a "SWAG" at it I would say that more than likely the loads that receptacle outlets are being asked to carry is forcing circuit designs to change. Circuit design is outside of the purview of the NEC.

    Just for example, think of the load that the receptacle(s) must service in a home theatre setup.

    A 15A receptacle circuit is normally calculated to handle a load of 12A. A 20A circuit can handle a load of 16A. In general terms you only plan for an 80% load on the over-current protection device (Circuit Breaker).

    Also, I prefer to use the correct receptacle for each circuit. Using a 20A receptacle on a 20A circuit, properly identifies the amperage available on the circuit. If you use a 15A receptacle on a 20A circuit, the person looking at the receptacle has no way of knowing that the circuit is 20Amps unless they go to the panel box and correctly identify the breaker serving that branch circuit.

    Any way, those are just my unsolicited personal opinions on the subject.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

I have a switch with power to it and wire going to a light,a wire going to outlets [ 3 Answers ]

I have a switch box with power to it and wire going to a light to the left out of the switch box and a wire going to outlets to the right out of the switch box. How do I wire the switch to make both the light and the outlets work properly?

Bathroom Lighting with Built-In Outlets [ 6 Answers ]

I am in the process of moving to a new apartment (one bedroom) in my building. The buildings are over 40 years old and the bathroom has the original bathroom lighting fixture (2 lights) with built-in power outlet (See photo below). ...

Outlets and lighting [ 1 Answers ]

Can you hook up outlets and lighting on the same breaker?

Can I mix outlets and lighting on one 20 amp circuit all with 12 g wire? [ 3 Answers ]

I have an open unfinished basement with a 20 amp circuit which supplies only a junktion box. It used to have a pull light on it. I have continued the 12 gage wire, which entered the junction box originating in the panel, from the junction box to two new floresent lights and ran further 12 gage...

Two wire outlets [ 6 Answers ]

I have home built in 1945 in Michigan. How do I put in in the new grouded outlets with two wires? One wire is coated and one is bare copper wire! Thanks for the help. Should I just have a electrican do it ? When I bought the house in 1973 I had the service panal replaced to a100amp service with...


View more questions Search