    Why does the code require a #2 wire for a 100 amp double-pole
    1) I have wired a subpanel feed with #2 ( or #3) wires protected with a 2 pole 100amp breaker. I am confused on why the code requres this. Doesn't each wire only carry half the load (50 A) max.

    2) Does a subpanel on a second floor require a grounding rod (or water pipe) connection, or just the ground wire back to the main panel?

    3) Is the bonding lug ( connected to grounding wire) sufficient to ground the sub-panel, or does the ground bar have to be bonded?

    4) Will a 1-1/4 inch flex conduit be large enough for 3-#2 wires and a #8 ground wire
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Oct 1, 2010, 05:16 AM
    My answers follow your questions.


    I have wired a subpanel feed with #2 ( or #3) wires protected with a 2 pole 100amp breaker. I am confused on why the code requres this. Doesn't each wire only carry half the load (50 A) max.

    Each pole of a 100 amp breaker can handle 100 amps, so the wire feeding it must be rated to handle 100 amps.

    2) Does a subpanel on a second floor require a grounding rod (or water pipe) connection, or just the ground wire back to the main panel?

    Any panel that is remote from the Main Breaker must be supplied with a four wire feeder, which includes an equipment ground that you mention.

    3) Is the bonding lug ( connected to grounding wire) sufficient to ground the sub-panel, or does the ground bar have to be bonded?

    An equipment ground bar must be bolted directly to the metal box of a panel with machine thread screws. The Neutral bar in a panel that doens not contain the Main Service Disconnecting Means does not get bonded to equipment ground.

    4) Will a 1-1/4 inch flex conduit be large enough for 3-#2 wires and a #8 ground wire

    Assuming THHN or XHHW insulation on the #2, yes, it will fit.
    cruiser2000's Avatar
    cruiser2000 Posts: 5, Reputation: 1
    New Member
     
    #3

    Oct 6, 2010, 02:05 AM
    Thank you for your answer.. Sorry still confused.

    If each pole can deliver 100 amps isn't that 200 amps, or 120v x 200amps = 2400Kva?

    A double pole breaker is made up of 2-50 amp breakers physically connected with a common trip bar labeled 100 amps.

    I know it may just be a naming convention but it's confusing to an old engineer like me.
    cruiser2000's Avatar
    cruiser2000 Posts: 5, Reputation: 1
    New Member
     
    #4

    Oct 6, 2010, 02:18 AM
    Comment on cruiser2000's post
    Sorry for calculation error 24 Kva or 24000 watts
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Oct 6, 2010, 02:45 AM
    If you were to cut a 2 pole 50 amp breaker in half, you would have two separate single pole breakers each rated 50 amps.

    A 100 amp service is 240 volts, 100 x 240 = 24000 VA.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

20 amp double pole gfci [ 9 Answers ]

I am working on an addition and am installing a whirlpool tub. The tub requires 2 - 20 amp GFCI protect circuits: 1 for the pump and 1 for the heater. I ran 12/3 wire in the walls thinking I could have the BLACK wire go from 1 GFCI breaker to the pump outlet and the RED wire go from a 2nd GFCI...

What size wire for 220v 100 amp service at 100 feet [ 7 Answers ]

I am running 220v 100 ft to a 125 amp sub panel. A welder would be the heaviest thing used. (around 200 amp welder) what size copper wire would I need running in pvc underground

How to wire a 20 amp double pole breaker using 10/3 copper wire [ 1 Answers ]

I have a water pump I would like to wire for 208 /220v. I have 10/3 copper wire. I need to wire the circuit breaker for the 208 / 220 v and connect the pump.

How do I wire a 10/2 wire to a double pole Breaker for 240 V? [ 6 Answers ]

I have recently baught a construction heater to wire into my garage. When speaking to the electrician at the store, he gave me all the advice my friend (who is a master's electrician) did. When I got home, I noticed that the wire he sold me to connect to a double pole Stab-lok 30A breaker was a...

Double pole 15 amp GFCI [ 1 Answers ]

I read the other note on gfci, but I have a different problem. I am installing a compressor outside the house in a shed, and I want to install an outside electrical socket on my outside wall of the house. The compressor requres 240V 15 Amps. I was planning on running a large extension cord to the...


View more questions Search