    When I give a load of a to generator it become off, please tell me what I should do?
    When I give a load of a freezer to generator it become off,please advice me that what I should do?
    My generator 3kv.
    smoothy's Avatar
    smoothy Posts: 25,492, Reputation: 2853
    Uber Member
     
    #2

    Jun 14, 2012, 08:50 AM
    Quote Originally Posted by laloopakori View Post
    when i give a load of a freezer to generator it become off,please advice me that what i should do?
    my generator 3kv.
    Must be a small freezer... most I have seen take a lot more than that to run due to the strartup surge requirements of the motor.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Jun 14, 2012, 01:02 PM
    You wrote 3kv, which means 3000 volts.I doubt that is correct.

    What size generator in watts, kilowatts, or VA or kilovolt-amps?

    Voltage?

    What size refrigerator in watts or amps?
    smoothy's Avatar
    smoothy Posts: 25,492, Reputation: 2853
    Uber Member
     
    #4

    Jun 15, 2012, 04:50 AM
    Good point... I had assumed they meant a 3KW portable generator... as that's a common size. Since English is not their first language.
    laloopakori's Avatar
    laloopakori Posts: 2, Reputation: 1
    New Member
     
    #5

    Jun 15, 2012, 12:24 PM
    Freezer load is two ampers
    And generator is 3000 watts.
    Please tell me what I should do.
    Reply me as soon as possible.
    smoothy's Avatar
    smoothy Posts: 25,492, Reputation: 2853
    Uber Member
     
    #6

    Jun 15, 2012, 12:30 PM
    Get a bigger generator Like 5,000 watt or bigger. The 2 amp is running current... the start up current every time the motor has to start is far higher and tripping the breaker. And since the compressor will cycle on an off often... you have to plan for the MAXIMUM load... which is startup.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Load testing a generator [ 1 Answers ]

Can I use a 208 volt 400 Hz load bank to test a 240v 60hz generator? Pete

Generator load sharing [ 5 Answers ]

:) respected sir I have one generator having 250kva capacity.I want to connect the existing load with this generator ,existing load is 140kw.and also tell me how I have share the load equally

Generator load for one house? [ 1 Answers ]

Hi.. m getting shifted to an apartment in a couple of months.. can anyone please help me the generator load required to run 6 houses of an apartment and the approximate fuel consumption for the same on hourly basis...

How to select generator for house load [ 3 Answers ]

I want to connect generator for my house ,please can you explain it with using diagram

Load in Generator [ 1 Answers ]

Why minimum load is required in ideal running generator.:o


View more questions Search