    What's the hazzard using different size wire
    What's the hazzard of going from a 20gage wire to a 15 gage wire when installing an emergency exit light
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Feb 7, 2012, 07:32 AM
    Well it is over kill.

    14 AWG conductors will work, but it would be smarter and easier to work with the 20 AWG wire.

    Now if you really meant 12 AWG conductors, then the answer is much clearer.

    If you splice 12 AWG wire to 14 AWG wire, then you must protect the entire circuit with a 15 amp breaker.

    You cannot use a 20 amp breaker with 14 AWG wire in the circuit,
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Feb 7, 2012, 10:27 AM
    Exactly where will this #20 AWG wire be installed?

    Minimum size building wire allowed will be #14, minimum size wire used in a fixture would be #16.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size & conduit size for 60 am subpanel 150 from source [ 9 Answers ]

Indiana question: I want to install a 60amp subpanel 150 feet from the main panel. This is all exposed runs both inside and out in a commercial envirenement. What gauge and type of copper wire and what size conduit whould I use. How often should insert a junction box in the run. John

What size wire do I need to run to get a 100amps. 225ft. using direct burial wire? [ 5 Answers ]

What size wire do I need to run to get a 100amps. 225ft. using direct burial wire coming from a 200amp. Service? Any info. Would be appreciated. Regards, Garry

Sub Panel AMP Size and Supply Wire Size [ 1 Answers ]

I would like to install a sub panel in my garage I was told to run 6/3 Romex to supply the sub panel and have done so. The run is about 65 feet and I am now wondering after reading this site what is the max I can get for this size wire? I plan to supply a compressor (20 amp) and the garden...


View more questions Search