    What size wire would I use to connect a 12KW generator to the transfer switch 100' .
    I want to install a 12KW standby generator, it comes with a load managed transfer switch. The generator will be approximately 80 feet from the transfer switch. I'm wondering what size wire should I use between them. The transfer switch will switch the entire load on a 200 amp panel in which we have selected circuits that we want to have on standby. The balance of the house on on another 200 amp panel that isn't backed up.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Mar 16, 2010, 07:37 AM
    I would use #4 copper.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Wire size between 18KW generator and 200A auto transfer switch [ 4 Answers ]

There is a 85 amp, 2 pole breaker at gen output that feeds the wire to the xfer switch. Is 1 gauge aluminum wire sufficient size for current conductors? 2 gauge for neutral and 3 gauge for ground? The NEC handbook has my head swimming. Thanks, Steve

Connect generator to transfer switch [ 12 Answers ]

I recently purchased a generator that has a 4 prong 30 amp outlet. I want to connect it to a 20 amp transfer switch, also 4 prong. I have 10 gauge wire, and bought the male and female ends. The problem (maybe) is that I bought 20 amp male and female ends. Should I have bought 30 amp? Thank...

How to connect a transfer switch using L14-20 to generator with L5-30 socket? [ 25 Answers ]

Years ago an electrician wired in a transfer switch that has an L14-20 connector on its face, and ran a heavy cord from there to the garage where the cord also terminates in an L14-20 plug (male). My old contractors generator had a socket connection for L14-20, but I'm looking to replace it...

Generator transfer switch [ 1 Answers ]

How difficult is it to install a generator transfer switch? It's pre-wired, doesn't look too Difficult. Is there anything I should look out for? The only thing I'm not sure of is it comes with two 15-amp 1-pole breakers, two 20-amp 1-pole breakers, and one 2-pole 20 amp breaker. How do I tell the...

3 wire 220 connecting transfer switch to generator [ 2 Answers ]

I have a manual transfer switch that I want to use between my house circuits and my 5000 watt generator. I have 3 wire #10 receptical existing from the circuit box over to where my generator sets (it is exhausted outside). Can I use this 3 wire line to connect my transfer switch to my generator...


View more questions Search