    What size of wire do I use
    I have a 200 amp main panel and would like to know what wire size do I need for a 125 amp sub panel that's about 55' feet away from the main panel.The 125 amp sub panel is going to be used for a in-law unit in the back yard.The unit is about 400 sq ft, a small room, living room, bathroom, kitchen with a small 24" electric stove and refrigerator.Also the sub panel in the main house is a 100 amp, did I screw up by buying the 125 amp sub panel for the in-law unit. I bought the murray brand because it had more spaces.The last 20' ft is under ground what p.v.c size do I use.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Sep 18, 2009, 06:15 AM
    Using NEC table 310.15 (B)(6) Special Ampacity rating for service and feeder cables you need a 2/3 feeder cable. It must be a four conductor run to the panel at the in-law residence.

    Because you have a Main Panel and an Existing Sub panel and a new planned 125 amp subpanel, I strongly urge you to get a load calculation assessment completed, by a licensed electrician and to make sure you have the required electrical permits in place.

    This study will also make sure that you are within the capacity of your 200 Amp service.

    I also urge you to consider using the services of a licensed electrician to run the feeder and make sure that the wiring of the new sub panel is up to code.
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #3

    Sep 19, 2009, 06:05 PM

    The size of the sub panel does not matter. You limit the service going to it with the breaker in the main panel. In other words you have a 125 sub panel but you limit the service with a 60 amp breaker in the main panel. The main breaker in the sub panel then becomes only a disconnect switch. The size of the breaker in the main panel is determined by the size wire used. Wire size determined by the calculated load.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size & conduit size for 60 am subpanel 150 from source [ 9 Answers ]

Indiana question: I want to install a 60amp subpanel 150 feet from the main panel. This is all exposed runs both inside and out in a commercial envirenement. What gauge and type of copper wire and what size conduit whould I use. How often should insert a junction box in the run. John

Sub Panel AMP Size and Supply Wire Size [ 1 Answers ]

I would like to install a sub panel in my garage I was told to run 6/3 Romex to supply the sub panel and have done so. The run is about 65 feet and I am now wondering after reading this site what is the max I can get for this size wire? I plan to supply a compressor (20 amp) and the garden...

Vintage stove- 3 wire 220v, what size wire? [ 1 Answers ]

We recently purchased a vintage Crosley range. The old wire was a 3-wire 220v, connected to terminals in the back- the black and red wires were actually 6 or so copper strands, and the white was a silver metal. My question is, what amperage do you think I need? Will 10 be enough? Thanks for your...

Wire Size and panel size [ 6 Answers ]

I have a separate small living quarters that is a single room that is about 180 feet away from the main panel. It is going to get another little bed room a small kitchen and a bathroom also maybe a washer. The main panel is a 100 amp meter socket combo. What should I upsize the main panel to? ...

4 wire home service entrance wire size [ 1 Answers ]

Mobile home requires 4 wire electrical service entrance wire. Distance is 160 foot from meter to breaker panel. 220V service. What size wire do I use? Can I use diff. size for neutral and ground?


View more questions Search